Definitions
Sequence – refers to how the drive is started, stopped, and told which direction to run.
When the sequence comes from the digital operator (local), the drive is started and stopped
using the "RUN" and "STOP" keys on the digital operator, and direction is given via the
"FWD/REV" key. Sequence can also come from the drive's control terminals (remote)
using either two-wire or three–wire control. The sequence inputs to the drive do NOT
require any outside voltages to activate them. Instead, contact closures (either from
switches, relay contacts or open collector circuits) activate the sequence inputs. Other
sequence sources are available, consult the Drive Technical Manual TM4315 for details.
Two-wire sequence – utilizes a "maintained" switch or relay contact. It is used on
applications where it is desirable to have the drive restart on restoration of power. It
should not be used where safety of attending personnel might be threatened by a
restart. This method is generally restricted to unattended fans & pumps, or where
another controller is entrusted with the decision to restart. Direction is controlled by
maintaining either a forward run or a reverse run command.
Three-wire sequence – utilizes "momentary" buttons or switches. This control
scheme emulates the traditional 3-wire motor starter control. A momentary closure of
a normally open run switch latches the drive in the RUN
mode (STOP switch must be closed or the drive will not
accept the momentary RUN command). A momentary
opening of the normally closed STOP switch unlatches
RUN mode bringing the drive to a stop. The three-wire
sequence is used where it would be dangerous for the
drive to restart after a power outage. This method
requires an intentional restart, as the RUN command is
unlatched immediately on loss of power. Direction is
determined by another maintained contact closure (closed = reverse).
Reference - The frequency reference tells the drive how fast to run the motor. There are
several source options for the frequency reference. First, the frequency reference can come
from the digital operator (local). Simply put, the motor speed can be entered into the
keypad. Second, the frequency reference can come from an analog signal (remote), such
as 0 to 10 Volts DC. When 0 Volts is applied to the drive, the drive will run at zero speed.
When 10V is applied to the drive, it will run at full speed. Apply anything in between and the
drive will run at that corresponding frequency (2.5VDC = 25% speed = 15 Hz). Other
reference sources are available, consult the Drive Technical Manual TM4315 for details.
Local Control – is when the sequence and/or reference comes from the digital operator
Remote Control – is when the sequence and/or reference comes from the control
terminals.