Table A1-1. Drive Parameters - Continued
PARA-
METER
NAME
Multi-function Input
n053
Selection 4 (Terminal S4)
Multi-function Input
n054
Selection 5 (Terminal S5)
Multi-function Input
n055
Selection 6 (Terminal S6)
n056
Multi-function Input
Selection 7 (Terminal S7)
Multi-Function Output
n057
Selection 1
(Terminals MA, MB & MC)
Multi-Function Output
n058
Selection 2
(Terminals P1 & PC)
Multi-Function Output
n059
Selection 3
(Terminals P2 & PC)
``
Analog Frequency Reference
n060
Gain (term. FR to FC) note 4
Analog Frequency Reference
n061
Bias (term. FR to FC) note 4
Analog frequency reference
n062
filter time constant
(term. FR to FC) note 4
Frequency Reference Loss
n064
Detection
Monitor Output
n065
Selection
Multi-function Analog Output
n066
(Terminals AM & AC)
n067
Analog Monitor Gain note 4
Analog Frequency Reference
n068
Gain (CN2, Voltage Ref Input)
Analog Frequency Reference
n069
Bias (CN2, Voltage Ref Input)
SETTING RANGE
(AND UNITS)
9: Multi-step speed ref. cmd. D
10: JOG Selection
11: Accel/Decel time change cmd.
12: External Base Block (N.O.)
13: External Base Block (N.C.)
14: Speed search from max. freq.
15: Speed search from set freq.
16: Accel/Decel hold command
17: Remote/Local selection
18: Serial Communication / control ckt.
selection
19: Fast Stop - Fault (N.O.)
20: Fast Stop - Alarm (N.O.)
21: Fast Stop - Fault (N.C.)
22: Fast Stop - Alarm (N.C.)
23: PID control off
24: I value reset (PID)
25: I value hold (PID)
26: Over Heat Pre-alarm OH3
27: Accel/Decel Time Select 2
34: Up
0: Fault
1: During running
2: Speed Agree
3: Zero Speed
4: Frequency detection 1
5: Frequency detection 2
6: Overtorque detection (N.O.)
7: Overtorque detection (N.C.)
8: Undertorque Detection (N.O.)
9: Undertorque Detection (N.C.)
10: Minor Fault
11: During Base Block
12: Local / Remote
13: Ready
20: Frequency Reference Loss Detect (N.O.)
21: Overheat Pre-alarm OH3 (N.O.)
14: During auto restart
15: During undervoltage
16: During reverse run
17: During speed search
18: Serial Comm. Controlled
19: PID feedback loss
0 to 255
-100 to 100
0.00 to 2.00
0: No Detection
1: Continue to run at 80% of max. frequency
0: Analog monitor output
1: Pulse monitor output
0: Output frequency (10V = 100% Fmax)
1: Output Current (10V = 250% drive
rated current)
2: DC Bus Voltage
(10V = 400 VDC [800 VDC])
3: Motor Torque
(10V = Motor rated torque)
4: Output Power
(10V = Drive Capacity kW)
5: Output Voltage 10V = n012 (voltage max)
6: Frequency Reference
0.00 to 2.00
-255 to 255
-100 to 100
A1-3
SETTING
FACTORY
USER
INCREMENT
SETTING
SETTING
1
5
(5)
1
6
(6)
1
7
(7)
1
10
(10)
1
0
1
1
1
2
1 (%)
100
1 (%)
0
0.01 (sec)
0.10
1
0
1
0
1
0
0.01
1.00
1%
100
1%
0
PARA.
REF.
5.18
5.19
5.8
5.17
5.17
5.32