Sampling Processing/Travel Average Processing Designation - Mitsubishi Electric AJ65BT-68TD User Manual

Thermocouple temperature input module
Table of Contents

Advertisement

3. SPECIFICATIONS
Downloaded from
ManualsNet.com
3.8.5

Sampling processing/travel average processing designation

The AJ65BT-68TD may designate sampling processing or travel average processing for each
individual channel.
The setting of sampling processing or travel average processing is made through the CH.
processing/travel average processing designation flags (RYn8 to RYnF).
Setting
ON
Travel average processing
OFF
Sampling processing
(1) Travel average processing
The average of the four detected temperature values that have been taken during each sampling
time (current value + three previous values) is calculated and stored in the remote register.
Also, since the average processing travels for each sampling, the most recent measured
temperature value may be obtained.
By using this, a scaling value can be obtained using the detected temperature value that has
undergone the average processing and stored in the remote register.
[°C]
The data transition inside the remote register
1st storage
+
+
4
search engine
Description
Sampling time
Time [ms]
2nd storage
+
+
+
+
4
3-18
MELSEC-A
Remote register
1st storage
Detected
2nd storage
temperature
value
3rd storage
3rd storage
+
+
+
4
sampling

Advertisement

Table of Contents
loading

Table of Contents