l Wiring of extension antenna cable
1.
Use the provided extension antenna cable to connect the antenna connector with the ex-
ternal antenna. Tighten the connector of the antenna extension cable with a torque of 2 to 3
N∙m. Refer to the specification about the limitation of bend radius when fixing or wiring.
2.
When using two extension cables, the provided arrester should be inserted between these
cables.
3.
Before the wiring work, confirm the polarities (male/female) of the connectors of antenna,
extension antenna cable, and arrester.
Tighten the connector of the antenna extension cable with a torque of 2 to 3 N∙m.
Protect by
Self-bonding tape
Housing of YFGW510
Figure C5-8 Wiring for remote antenna
l Ground wiring of arrestor for antenna extension cables
To connect two antenna extension cables, an arrestor for lightning protection is provided. Place
the arrestor between the two extension cables. Connect the grounding cable to the ground termi-
nal of the arrestor.
Connect the grounding cable to the grounding terminal on the main body. Class D grounding (the
third class grounding) with the grounding resistance of 100 Ω or less is necessary. Do not share
the ground with other devices.
ISA100.11a antenna
Protect by
Self-bonding tape
Antenna Extension Cable 1
Select from Length 3m
<C5. Wiring>
ISA100.11a antenna
Antenna Extension Cable 2
Select from Length 10m
Arrestor
Ground wiring
Antenna Extension Cable 1
Select from Length 3m
Housing of YFGW510
C5-10
FC0508.ai
IM 01W02E01-01EN