C1. Installation Environment

YFGW510 should be installed in appropriate conditions to ensure its stable operation.
The table below shows details of the installation environment for YFGW510.
Item
Power supply
Terminal
Maximum power consumption
Grounding
Operating
Temperature
range
Transport/storage -40 to 85°C
Operating
Humidity
range
Transport/storage 0 to 100% RH (No condensation)
Operating
Temperature
gradient
Transport/storage ±20°C/h or less
Protection degree
Vibration resistance
Shock resistance
Altitude
Electric field
Noise
Electrostatic
resistance
discharge
Cooling
Mounting
IMPORTANT
• Avoid direct sunlight.
• Keep away conductive particles such as iron and carbon.
• Avoid corrosive gases such as hydrogen sulfide, sulfurous acid, chlorine and ammonia.
<C1. Installation Environment>
Environment
Rated voltage
24 V DC
Voltage range
10 to 26.4 V DC
Momentary power
1 ms or less (instant
failure
disconnection)
Ripple ratio
1%p-p or less
M4 screw terminal (power supply and ground)
3.5 W
Class D grounding (100 ohms or less)
-40 to 65°C
0 to 100% RH (No condensation)
±10°C/h or less
IP66
Displacement amplitude: 0.21 mm (10 to 60 Hz)
Acceleration amplitude: 3 G (60 to 2000 Hz)
50 G 11 ms (de-energized, with half-sine wave
pulse in three directions)
3000 m or less
3 V/m or less (80 MHz to 1 GHz)
4 kV or less (contact discharge), 8 kV or less
(aerial discharge)
Natural air cooling
2-inch pipe
C1-1
Note
No sharing with other
devices
JEIDA29 class B
IEC529
IEC68-2-27
With dedicated brackets