Setting Operating Times - OEG 650 001 330 Installation And Operating Instruction

Multifunctional, capacity-controlled air/water heat pump
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 46
66
4.4.2.4
Changing the
operating mode
4.4.2.5

Setting operating times

GB
Auto temp. is an operating mode for automatic temperature setting of the heat pump,
subject to the ambient temperature according to the following auto-heat curve.
A. Whether the Auto Temp. operating mode is valid or not, depends on parameter P19.
0-setting means the mode is not valid, 1 means valid.
B. Shifting the automatic heating curve is defi ned by parameter P09. A positive value
means rising, a negative value means dropping (-10 °C ~10 °C).
C. The highest temperature of the automatic heating curve is defi ned by parameter P08,
from 30 ~50, standard 45. If the parameter is 45, the highest AU target temperature is
45 °C.
Click timer button
to set the operating time for the heat pump and C3 pump.
Multi-functional DC inverter air/water heat pump
P09
P09
P09
P09
-10 °C
-10 °C
+10 °C
+10 °C
Outside temperature in °C
P08 = 50 °C MAX
P08 = 50 °C MAX.
P08 = 45 °C STANDARD
P08 = 45 °C STANDARD
P08 = 35 °C MIN
P08 = 35 °C MIN.