Precautions for compliance with the EC Directive

Precautions when using the product
Attach a ferrite core to the power supply cable (on the Simple Motion module/Motion module side).
Attach the ferrite core with the cable wrapped around it two times at a location that is 200 mm or less from the Simple Motion
module/Motion module side connector.
For the ferrite core, use a core that is equivalent to the following:
• Model: ZCAT3035-1330 manufactured by TDK Corporation
Simple Motion
module/
Motion module
Ferrite core
Power supply cable
Power source of 24 V DC power supply voltage
Supply power to the 24 V DC power supply voltage of the FX5-SSC-S/FX5-SSC-G from the AC/DC power supply installed in
the same control panel.
APPX
88
Appendix 6 Standard Compliant Models