LED display specifications [FX5-SSC-G]
This section lists LED display specifications for FX5-SSC-G.
: OFF, : ON, ●: Flashing
LED
READY LED
POWER LED
RUN LED
ERROR LED
D LINK LED
SD/RD LED
L ER LED
LINK LED
*1 Includes cyclic transmission and transient transmission data for CC-Link IE TSN.
The error status can be categorized as shown below based on the ON status of the RUN LED and ERROR LED.
When multiple errors occur, the error status is displayed in the order of Major error > Moderate error > Minor error.
RUN LED
OFF
ON
ON
Downloaded from
ManualsNet.com
Description
Displays the PLC READY status.
Displays the power status.
Displays the operation status.
Displays the error status.
Displays the data link status.
Displays the data transmit status.
Displays the port status.
Displays the link status.
ERROR LED
Error status
ON or flashing
Major error
Flashing
Moderate error
ON
Minor error
search engine
LED display
Status
READY
PLC READY ON
READY
PLC READY OFF
POWER
Power ON
POWER
Power OFF
RUN
Normal operation
RUN
Error occurring
ERROR
Error occurring
ERROR ●
200 ms interval: error occurring
500 ms interval: erroneous data link station detected
ERROR
Normal operation
D LINK
Data link (cyclic transmission)
D LINK ●
Data link (cyclic transmission stopped)
D LINK
Data link not started (released)
*1
SD/RD
Data
transmission in progress
*1
SD/RD
Data
transmission not in progress
L ER
Abnormal data received
L ER
Normal data received
LINK
Link up
LINK
Link down
Description
An error in which the module stops operation because of a hardware error or memory
error, etc.
An error related to module operation in which the module stops operation because of a
parameter error, etc.
An error, such as a communication, positioning control, or program error, in which the
module continues operation.
1 PART NAMES
1.1 LED Display Specifications
1
19