Chapter 3 Installing The Drive; Mechanical Installation; Mounting The Drive; Ventilation - Parker AC650V Series Product Manual

Frame 1, 2 & 3
Table of Contents

Advertisement

3-1
Installing the Drive
I
NSTALLING THE
Chapter 3
IMPORTANT: Read Chapter 10: "Certification for the Drive" before installing this unit.

Mechanical Installation

D
SIDE VIEW - Frame 1 illustrated
Fixing
Torque
Frame 1
M4
1.5Nm
Frame 2
M5
3.0Nm
Frame 3
M5
3.0Nm

Mounting the Drive

DIN Mounting

Ventilation

The DIN clip is repositioned on Frames 1 and 2
to provide the upper fixing hole when wall-mounting
DIN
centreline
H2
REAR VIEW - Frame 1 illustrated
Weight
H1 Fixing Centres
0.85kg
(2 lbs)
(5.2")
1.4kg
(3 lbs)
(7.4")
2.7kg
(6 lbs)
(9.5")
To maintain compliance with European Electrical Safety Standard VDE0160(1994)/EN50178
(1998) the unit must be mounted inside a control cubicle that requires a tool for opening. The
cubicle should provide 15dB attenuation to radiated emissions between 30-100MHz.
Mount the drive vertically on a solid, flat, non-flammable, vertical
surface. It can be panel-mounted, or rail-mounted on a rail
complying with EN50022 (35mm DIN).
To DIN mount the unit, hang the unit on the top DIN rail and push
the unit onto the bottom DIN rail until it snaps in to position. Secure
with a lower screw fixing. To release the unit, use a flat bladed
screwdriver as shown.
Maintain a minimum air clearance for ventilation of 100mm (4 inches) above and below the
unit. When mounting two or more 650V units together, these clearances are additive. Ensure that
the mounting surface is normally cool. Be aware that adjacent equipment may generate heat and
also have clearance requirements. Provided the minimum clearance for ventilation is maintained,
650V drives may be mounted side-by-side.
D
RIVE
W
C
H3
H1
W
2
(Frame 2 similar)
H2
132
143
(5.6")
188
201
(7.9")
242
260
(10.2")
H3
centreline
H4
H2
DIN centreline
H4
W
REAR VIEW - Frame 3
H3
H4
C
35
139
6
(1.4")
(5.5")
(0.2")
35
194
6.5
(1.4")
(7.7")
(0.24")
38
112
5
(1.5")
(4.4")
(0.2")
Dimensions are in millimetres ( inches )
W
C
DIN
H1
2
W
D
73
142
(2.9")
(5.6")
73
173
(2.9")
(6.8")
96
200
(3.8")
(7.9")
lower
fixing
hole
650V AC Drive

Advertisement

Table of Contents
loading