Digital Inputs; Digital Outputs; Cabling Requirements For Emc Compliance - Parker AC650V Series Product Manual

Frame 1, 2 & 3
Table of Contents

Advertisement

9-6
Technical Specifications

Digital Inputs

Operating Range
Input Current
Sample Interval

Digital Outputs

Nominal Open
Circuit Output
Voltage
Nominal Output
Impedance
Rated Output Current

Cabling Requirements for EMC Compliance

Cable Type
(for EMC Compliance)
Segregation
Length Limitations
With Internal AC Supply
EMC Filter
Length Limitations
Without Internal AC
Supply EMC Filter
Screen to Earth
Connection
Output Choke
* Maximum motor cable length under any circumstances
DIN1, DIN2, DIN3, DIN4, DIN5:
0-5V dc = OFF, 15-24V dc = ON
(absolute maximum input voltage ±30V dc)
IEC1131
DIN6, DIN7:
0-1.5V dc = OFF, 4-24V dc = ON
(absolute maximum input voltage ±30V dc)
IEC1131
7.5mA @ 24V
10ms
DOUT1 and DOUT2
23V (minimum 19V)
47
50mA
(either individually or as the sum of outs from terminals 6, 10 & 11)
Power Supply Cable
Motor Cable
Unscreened
Screened/armoured
From all other wiring
From all other wiring (noisy)
(clean)
Unlimited
*25 metres
Unlimited
25 metres
Both ends
300 metres
maximum
24V
15V
5V
0V
24V
4V
1.5V
0V
Brake Resistor Cable
Signal/Control Cable
Screened/armoured
Screened
From all other wiring
(sensitive)
25 metres
25 metres
25 metres
25 metres
Both ends
Drive end only
ON
undefined state
OFF
ON
undefined state
OFF
650V AC Drive

Advertisement

Table of Contents
loading

Table of Contents