Wiring

2.1 Wiring
2.1.1

Terminal connection diagram

Sink logic
*1. DC reactor
Be sure to connect the DC reactor
Main circuit terminal
supplied with the FR-A760-01040 or
more.
Control circuit terminal
When using the FR-A760-00840 with LD
or SLD set, always use a DC reactor
(option).
When a DC reactor is connected to the
FR-A760-00840 or less, remove the
jumper across P1-P/+.
Three-phase AC
power supply
*2. To supply power to the
control circuit separately,
remove the jumper across
R1/L11 and S1/L21.
Control input signals (No voltage input allowed)
Terminal functions vary with
the input terminal
assignment (Pr. 178 to Pr. 189)
(Refer to page 217)
holding selection
Multi-speed
selection
*3. JOG terminal can be used
as pulse train input terminal.
Use Pr.291 to select
JOG/pulse.
Second function selection
*4. AU terminal can be
used as PTC input
terminal.
Terminal 4 input selection
(Current input selection)
Selection of automatic restart
after instantaneous
power failure
Contact input common
(Common for external power supply transistor)
Frequency setting signal (Analog)
Frequency setting
potentiometer
1/2W1k Ω
*6
* 5. Terminal input specifications
can be changed by analog
input specifications
Auxiliary
switchover (Pr. 73, Pr. 267).
input
Set the voltage/current input
switch in the OFF position to
Terminal
select voltage input (0 to 5V/0
4 input
to10V) and ON to select
(Current
current input (4 to 20mA).
input)
(Refer to page 271)
*6 . It is recommended to use 2W1kΩ
when the frequency setting signal
is changed frequently.
CAUTION
· To prevent a malfunction due to noise, keep the signal cables more than 10cm
main circuit wire of the input side and the output side.
· After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
· Set the voltage/current input switch correctly. Different setting may cause a fault, failure or malfunction.
14
Earth
(Ground)
MC
MCCB
R/L1
S/L2
T/L3
R1/L11
Jumper
S1/L21
*2
Earth
(Ground)
Forward
STF
rotation
start
STR
Reverse
rotation
start
STOP
Start self-
RH
High speed
RM
Middle
speed
RL
Low speed
JOG
Jog mode
RT
MRS
Output stop
RES
Reset
AU
CS
SD
PC
24VDC power supply
10E(+10V)
10(+5V)
3
2
2
5
1
(+)
1
(-)
(+)
4
(-)
Connector
Option connector 1
for plug-in option
connection
Option connector 2
Option connector 3
Brake unit
*1
(Option)
R
*7
Jumper
Jumper
P1
P/+
PX
PR
N/-
Inrush current
limit circuit
Main circuit
Control circuit
*3
*4
AU
PTC
24V
PU
connector
*5
Voltage/current
input switch
4 2
ON
USB
OFF
connector
0 to 5VDC
(Initial value)
0 to 10VDC
selected
*5
0 to 20mADC
(Analog common)
0 to ± 10VDC
(Initial value)
selected
0 to ± 5VDC
*5
4 to 20mADC
(Initial value)
0 to 5VDC
*5
selected
0 to 10VDC
RXD+
Terminating
resistor
(3.94inches)
*7. Brake resistor (accesories)
The brake resistor is provided with the FR-
A760-00061 or less. Connect the brake
resistor provided to P/+-PR .
Terminal PR is provided for the FR-A760-
00017 to 00330.
Install a thermal relay to prevent an overheat
and burnout of the brake resistor.
(Refer to page 38)
U
V
IM
W
Relay output
C1
Terminal functions
B1
Relay output 1
vary with the output
(Fault output)
terminal assignment
A1
(Pr. 195, Pr. 196)
(Refer to page 225)
C2
B2
Relay output 2
A2
Open collector output
RUN
Running
Terminal functions
SU
vary with the output
Up to frequency
terminal assignment
IPF
Instantaneous
(Pr. 190 to Pr. 194)
power failure
(Refer to page 225)
OL
Overload
FU
Frequency detection
SE
Open collector output common
Sink / source common
* 8. It is not necessary
*9. FM terminal can be
when calibrating the
indicator from the
operation panel.
+
-
Indicator
FM
(Frequency meter, etc.)
*9
Calibration
resistor * 8
SD
AM
(+)
Analog signal output
5
(-) (0 to 10VDC)
RS-485 terminals
TXD+
Data transmission
TXD-
Data reception
RXD-
SG
GND
VCC
(Permissible load
5V
current 100mA)
away from the power cables. Also separate the
(Refer to page 15)
Motor
Earth (Ground)
used for pulse train
output of open collector
output using Pr.291.
Moving-coil type
1mA full-scale