Mitsubishi Electric FR-A760 Series Instruction Manual page 234

Table of Contents

Advertisement

(2) 3-wire type (STF, STR, STOP signal)
⋅ A three-wire type connection is shown below.
⋅ The start self-holding selection becomes valid when the STOP signal is turned on. In this case, the forward/reverse
rotation signal functions only as a start signal.
⋅ If the start signal (STF or STR) is turned on and then off, the start signal is held and makes a start. When changing
the direction of rotation, turn STR (STF) on once and then off.
⋅ To stop the inverter, turning off the STOP signal once decelerates it to a stop.
Forward
Stop
rotation start
Reverse
rotation start
ON
STF
STR
STOP
ON
ON
OFF
Three-Wire Type Connection Example (Pr. 250 = "9999")
REMARKS
⋅ The STOP signal is assigned to the terminal STOP in the initial setting. By setting "25" in Pr. 178 to Pr. 189, the STOP signal can
also be assigned to the other terminal.
⋅ When the JOG signal is turned on to enable jog operation, the STOP signal becomes invalid.
⋅ If the MRS signal is turned on to stop the output, the self-holding function is not canceled.
(3) Start signal selection
STF
STR
OFF
OFF
OFF
ON
ON
OFF
ON
ON
♦ Parameters referred to ♦
Pr. 4 to Pr. 6 (Multi-speed setting)
Pr. 178 to Pr. 189 (Input terminal function selection)
STF
Inverter
STR
STOP
SD
Time
ON
OFF
Pr. 250 Setting Inverter Status
0 to 100s, 9999
Stop
Reverse rotation
Forward rotation
Stop
Refer to page 154
Refer to page 217
Function assignment of external terminal and control
Stop
Start
Forward rotation
/reverse rotation
ON
STF
ON
STR
STOP
ON
OFF
Three-Wire Type Connection Example (Pr. 250 = "8888")
1000s to 1100s, 8888
Stop
Forward rotation
Reverse rotation
STF
Inverter
STOP
STR
SD
Time
ON
OFF
223
4

Hide quick links:

Advertisement

Table of Contents
loading