Mitsubishi Electric FR-A760 Series Instruction Manual page 406

Table of Contents

Advertisement

Operation Panel
E.OC3
Indication
Name
Overcurrent trip during deceleration or stop
When the inverter output current reaches or exceeds approximately 220% of the rated inverter current
Description
during deceleration (other than acceleration or constant speed), the protective circuit is activated to
stop the inverter output.
1. Check for sudden speed reduction.
2. Check for output short circuit.
3. Check for too fast operation of the motor's mechanical brake.
Check point
4. Check that stall prevention operation setting is correct.
5. Check that the power supply for RS-485 terminal is not shorted. (under vector control)
6. Check that the rotation direction is not switched from forward to reverse rotation (or from reverse to
forward) during torque control under real sensorless vector control.
1. Increase the deceleration time.
2. Check the wiring to make sure that output short circuit does not occur.
3. Check the mechanical brake operation.
Corrective action
4. Check that stall prevention operation setting is correct.(Refer to page 138.)
5. Check RS-485 terminal connection. (under vector control)
6. Prevent the motor from switching the rotation direction from forward to reverse (or from reverse to
forward) during torque control under real sensorless vector control.
Operation Panel
E.OV1
Indication
Name
Regenerative overvoltage trip during acceleration
If regenerative energy causes the inverter's internal main circuit DC voltage to reach or exceed the
Description
specified value, the protective circuit is activated to stop the inverter output. The circuit may also be
activated by a surge voltage produced in the power supply system.
1. Check for too slow acceleration. (e.g. during descending acceleration in vertical lift load)
Check point
2. Check that the Pr. 22 Stall prevention operation level is not lower than the no load current.
1. ·Decrease the acceleration time.
Corrective action
·Use regeneration avoidance function (Pr. 882 to Pr. 886). (Refer to page 368.)
2. Set a value larger than the no load current in Pr. 22 Stall prevention operation level.
Operation Panel
E.OV2
Indication
Name
Regenerative overvoltage trip during constant speed
If regenerative energy causes the inverter's internal main circuit DC voltage to reach or exceed the
Description
specified value, the protective circuit is activated to stop the inverter output. The circuit may also be
activated by a surge voltage produced in the power supply system.
1. Check for sudden load change.
Check point
2. Check that the Pr. 22 Stall prevention operation level is not lower than the no load current.
1. ·Keep load stable.
·Use regeneration avoidance function (Pr. 882 to Pr. 886). (Refer to page 368.)
Corrective action
·Use the brake unit as required.
2. Set a value larger than the no load current in Pr. 22 Stall prevention operation level.
Operation Panel
E.OV3
Indication
Name
Regenerative overvoltage trip during deceleration or stop
If regenerative energy causes the inverter's internal main circuit DC voltage to reach or exceed the
Description
specified value, the protective circuit is activated to stop the inverter output. The circuit may also be
activated by a surge voltage produced in the power supply system.
Check point
Check for sudden speed reduction.
· Increase the deceleration time. (Set the deceleration time which matches the moment of inertia of
the load)
Corrective action
· Decrease the braking duty.
· Use regeneration avoidance function (Pr. 882 to Pr. 886). (Refer to page 368.)
· Use the brake unit as required.
Causes and corrective actions
FR-PU04
OC During Dec
FR-PU07
FR-PU04
OV During Acc
FR-PU07
FR-PU04
Stedy Spd OV
FR-PU07
FR-PU04
OV During Dec
FR-PU07
5
395

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents