(2) Set multiple torque boost (RT signal, X9 signal, Pr. 46, Pr. 112)
⋅ Use the second (third) torque boost when changing the torque boost according to application or when using
multiple motors by switching between them by one inverter.
⋅ Pr. 46 Second torque boost is made valid when the RT signal turns on.
⋅ Pr. 112 Third torque boost is valid when the X9 signal is on. For the terminal used for X9 signal input, set "9" in any of
Pr. 178 to Pr. 189 (input terminal function selection) to assign the X9 signal function.
REMARKS
⋅ The RT(X9) signal acts as the second
(Refer to page 221)
⋅ The RT signal is assigned to the RT terminal in the default setting. By setting "3" in any of Pr. 178 to Pr. 189 (input terminal function
selection), you can assign the RT signal to the other terminal.
CAUTION
⋅ Increase the setting value when the distance between the inverter and the motor is long or when the motor torque is insufficient
in the low-speed range. If the setting is too large, an overcurrent trip may occur.
⋅ The Pr. 0, Pr. 46, Pr. 112 settings are valid only when V/F control is selected.
⋅ Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions. Please
make setting after confirming the function of each terminal.
♦ Parameters referred to ♦
Pr. 3 Base frequency, Pr. 19 Base frequency voltage
Pr. 71 Applied motor
Refer to page 174
Pr. 178 to Pr. 189 (Input terminal function selection)
(third)
function selection signal and makes the other second
Refer to page 147
Refer to page 217
Adjust the output torque (current) of the motor
(third)
functions valid.