Communication operation and setting
(9) Setting items and set data
After completion of parameter setting, set the instruction codes and data then start communication from the computer
to allow various types of operation control and monitoring.
No.
Item
1
Operation mode
Output
frequency/
speed
Output
current
Output
voltage
Special
monitor
Special
monitor
2
selection No.
Fault
definition
Run command
(extended)
3
Run command
Inverter status
monitor
(extended)
4
Inverter status
monitor
Set frequency
(RAM)
Set frequency
(EEPROM)
Set frequency
5
(RAM)
Set frequency
(RAM, EEPROM)
6
Inverter reset
Fault definition
7
all clear
Refer to page 320 for data formats (A, A', B, B', C, D)
326
Read/
Instruction
Write
Code
H0000: Network operation
Read
H7B
H0001: External operation
H0002: PU operation
Write
HFB
H0000 to HFFFF: Output frequency in 0.01Hz increments
Read
H6F
Speed in 1r/min increments (when Pr. 37 = 1 to 9998 or Pr. 144 = 2 to
10, 102 to 110)
H0000 to HFFFF: Output current (hexadecimal) in 0.01A increments
Read
H70
Read
H71
H0000 to HFFFF: Output voltage (hexadecimal) in 0.1V increments
Read
H72
H0000 to HFFFF: Monitor data selected in instruction code HF3
Read
H73
H01 to H3C: Monitor selection data
Refer to the special monitor No. table (page 328)
Write
HF3
H0000 to HFFFF: Two most recent alarm definitions
H74 to
Read
H77
Refer to the fault data table (page 329)
Write
HF9
You can set the control input commands such as the forward
rotation signal (STF) and reverse rotation signal (STR). (Refer to
page 329 for details)
Write
HFA
Read
H79
You can monitor the status of the output signals such as forward
rotation, reverse rotation and inverter running (RUN). (Refer to page
330 for details)
Read
H7A
Read the set frequency/speed from the RAM or EEPROM.
H6D
H0000 to HFFFF: Set frequency in 0.01Hz increments
Read
Speed in 1r/min increments (When Pr. 37 = 1 to 9998 or Pr. 144 = 2
H6E
to 10, 102 to 110)
Write the set frequency/speed into the RAM or EEPROM.
HED
H0000 to H9C40 (0 to 400.00Hz) : frequency in 0.01Hz increments
H0000 to H270E (0 to 9998) : speed in r/min increments (when Pr.
Write
37 = 1 to 9998 or Pr. 144 = 2 to 10, 102 to 110)
HEE
⋅ To change the running frequency consecutively, write data to the
inverter RAM. (Instruction code: HED)
H9696: Resets the inverter.
⋅ As the inverter is reset at start of communication by the computer,
the inverter cannot send reply data back to the computer.
Write
HFD
H9966: Resets the inverter.
⋅ When data is sent normally, ACK is returned to the computer and
then the inverter is reset.
Write
HF4
H9696: Faults history batch clear
Data Description
(RS-485 communication operation via PU connector)
(FR-A760-00840 or less) / 0.1A increments (FR-
A760-01040 or more)
b15
b8 b7
H74
Second fault in past
H75
Fourth fault in past
H76
Sixth fault in past
H77
Eighth fault in past
b0
Latest fault
Third fault in past
Fifth fault in past
Seventh fault in past
Number of
Data Digits
(format)
4 digits
(B.E/D)
4 digits
(A,C/D)
4 digits
(B.E/D)
4 digits
(B.E/D)
4 digits
(B.E/D)
4 digits
(B.E/D)
2digits
(B.E'/D)
2digits
(A',C/D)
4 digits
(B.E/D)
4 digits
(A,C/D)
2digits
(A',C/D)
4 digits
(B.E/D)
2digits
(B.E'/D)
4 digits
(B.E/D)
4 digits
(A,C/D)
4 digits
(A,C/D)
4 digits
(A,D)
4 digits
(A,C/D)

Hide quick links: