Check the inverter type of the inverter you purchased. Appropriate peripheral devices must be selected according to
the capacity. Refer to the following list and prepare appropriate peripheral devices:
600V class
Motor Output
Applicable Inverter Type
(kW (HP))
*1
0.75 (1)
FR-A760-00017-NA
2.2 (3)
FR-A760-00040-NA
3.7 (5)
FR-A760-00061-NA
7.5 (10)
FR-A760-00120-NA
15 (20)
FR-A760-00220-NA
22 (30)
FR-A760-00330-NA
37 (50)
FR-A760-00550-NA
55 (75)
FR-A760-00840-NA
75 (100)
FR-A760-01040-NA
90 (125)
FR-A760-01310-NA
110 (150)
FR-A760-01520-NA
132 (200)
FR-A760-02210-NA
185 (300)
FR-A760-02550-NA
220 (350)
FR-A760-03040-NA
280 (450)
FR-A760-04020-NA
355(550)
FR-A760-04960-NA
450(700)
FR-A760-06630-NA
*1
Selections for use of the 4-pole standard motor with power supply voltage of 575VAC 50Hz.
*2
Select the MCCB according to the power supply capacity.
Install one MCCB per inverter.
For installations in the United States or Canada, use the class T type fuse certified by the UL and cUL.
(Refer to
Installation Guideline.)
*3
When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the inverter, etc. Identify
the cause of the trip, then remove the cause and power on the breaker.