Emc And Environmental Type Tests - Siemens SIMATIC NET RUGGEDCOM RSG2100F Installation Manual

Hide thumbs Also See for SIMATIC NET RUGGEDCOM RSG2100F:
Table of Contents

Advertisement

6.2

EMC and Environmental Type Tests

The RUGGEDCOM RSG2100F has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Tests per IEC 61850-3
Note
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
RUGGEDCOM RSG2100F
Installation Manual, 04/2022, C79000-G8976-1344-11
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General
Requirements
EN 50121-4
Railway Applications – Electromagnetic Compatibility – Emission and Immunity
of the Signaling and Telecommunications Apparatus
In the case of an all fiber port configuration, this product meets all Class 2
requirements. Otherwise, all Class 1 requirements are met for copper ports.
If the unit contains copper ports, the IEC 1613 conformance is Class 1, during
which disturbance errors may occur but recovery is automatic.
If the unit contains all fiber ports, the IEC 1613 conformance is Class 2, during
which no disturbance errors will occur.
Test
ESD
Radiated RFI
Burst (Fast
Transient)
Surge
6.2 EMC and Environmental Type Tests
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
AC Power Ports
Certification
Test Levels
Severity Levels
±8 kV
±15 kV
20 V/m
±4 kV @ 2.5 kHz
±4 kV
±4 kV Line-to-
Ground, ±2 kV
Line-to-Line
±2 kV Line-to-
Ground, ±1 kV
Line-to-Line
±4 kV Line-to-
Ground, ±2 kV
Line-to-Line
4
a
Note
a
Note
4
4
3
4
43