temporary communication loss, while Class 2 requires error-free and interrupted
communications.
Radiated RFI
Fast Transient
Oscillatory
HV Impulse
Oscillatory
Magnetic Field
Environmental Type Tests
60068-2-1
60068-2-2
60068-2-30
60068-21-1
60068-21-2
RUGGEDCOM RSG2100F
Installation Manual, 04/2022, C79000-G8976-1344-11
Description
ESD
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Dielectric
Signal Ports
Strength
DC Power Ports
AC Power Ports
Damped
Enclosure Ports
Test
IEC
Cold Temperature
IEC
Dry Heat
IEC
Humidity (Damp
Heat, Cyclic)
IEC
IEC
6.2 EMC and Environmental Type Tests
Description
Test Ad
Test Bd
Test Db
Vibration
Shock
Test Levels
±2 kV
±4 kV
±8 kV
±4 kV
±8 kV
±15 kV
35 V/m
4 kV @ 2.5 kHz
4 kV
4 kV
4 kV
2.5 kV Common Mode @ 1 MHz
2.5 kV Common
1 kV differential mode @ 1 MHz
2.5 kV Common
1 kV differential mode @ 1 MHz
5 kV (Fail-Safe Relay Output)
5 kV
5 kV
2 kV
2 kV
2 kV
100 A/m
Test Levels
-40 °C (-40 °F), 16 Hours
85 °C (185 °F), 16 Hours
95% (non-condensing),
55 °C (131 °F), 6 cycles
2g @ 10-150 Hz
30 g @ 11 ms
Certification
Severity
Level
 
 
 
 
 
45