5.6 RESTART
FOR SG-RB...-W MODELS
The Restart mode and Reset/Restart wire must be connected through a N.C. button to the 0V or 24V from
the power supply of the ESPE to select, respectively, manual restart or automatic restart.
The Reset/Restart wire can be used to enter alignment function when N.C. button is pressed at start-up.
The RESET/RESTART button must be located in such a way that the operator can check the
protected area during any reset operation (see section 3).

5.7 EXTERNAL RELAYS CONNECTION

Example: connection to the safety relay.
The previous figure shows the connection between the safety light curtains and the safety relay of the SE-
SR2 series functioning in the Automatic Restart mode (left side) and Manual Restart with monitoring (right
side).
Do not use varistors, RC circuits or LEDs in parallel at relay inputs or in series at OSSD
outputs.
The OSSD1 and OSSD2 safety contacts cannot be connected in series or in parallel, but
must be used separately (Figure 30), conforming to the plant's safety requirements.
If one of these configurations is erroneously used, the device enters the output failure
condition.