6.7.3 Override restart mode function

This function let the user choose, setting dip-switches of RX device (see section 5 – "ELECTRICAL
CONNECTIONS AND CONFIGURATION"), the restart mode after Override when ESPE is configured in
manual restart mode, and in particular to force automatic restart mode of light curtain as shown in Figure 47.
BEAMS

OVERRIDE STATUS

OSSDs
Override with automatic restart function, allows to restart automatically the normal
working of the curtain (normal operation condition) when the detection area (curtains +
sensors) is cleared.
This function does not comply with the requirements of IEC 61496-1, because it is a forcing of the safety
condition.
For this reason, all possible risks must be considered and related precautions undertaken.
It is recommended that:
all control operations must be assigned only to a well-trained and skilled personnel;
the user assigned to the actuation of the override function, must be able to work in a
condition of maximum surveillance and visibility of the whole area.
6.7.4 Override status
When the device enters the Override status, OVERRIDE STATUS PNP output line provided on M12 12 RX
connector (see section 5 – "ELECTRICAL CONNECTIONS AND CONFIGURATION") switches from 0Vdc to
24Vdc, providing electronic information to the user.
OVERRIDE STATUS
OVERRIDE STATUS
PNP OUTPUT
Forced
condition
Figure 47
Figure 48
50
OBSCURED
FREE
ON
OFF
NORMAL
OPERATION
SAFE
ON
OFF
24Vdc
0Vdc