Technical data
5.4 Interfaces and performance features
Fail-safe digital inputs/outputs
Table 5-14
Number of inputs
Input voltage
Electrical isolation
Current consumption typical at 1 signal level
Input delay, typical (hardware)
Protection
The digital inputs are protected against polarity reversal up to -30 V
1)
2)
Reference potential for DI 16, DI 18, DI 20 and DO 16 is terminal M1 (X120, X130)
Up to and including hardware version "C" for D410-2 DP or "B" for D410-2 DP/PN
3)
Table 5-15
Number of outputs
Rated load voltage, permissible range
Electrical isolation
Current load, max.
Residual current, max.
Output delay time,
typ./max. (hardware)
Permissible quiescent current
Protection
Data for: V
1)
Analog input
Table 5-16
Number of inputs
Galvanic isolation
Common-mode range
90
Technical data for fail-safe digital inputs (F-DI)
Rated value
For signal "1"
For signal "0"
1)
2)
Signal "0" → "1"
Signal "1" → "0"
Technical data for fail-safe digital output (F‑DO)
1)
Signal "0" → "1"
Signal "1" → "0"
= 24 V; load 48 Ω; high ("1") = 90% V
cc
Technical data for the analog input
3 F-DI (or as 6 DI)
24 VDC
15 ... 30 V
-3 ... +5 V
Yes (via optocoupler)
3.5 mA at 24 V
5 mA at 24 V
3)
50 μs
150 μs
Short circuit, ground fault and overload proof
1 F-DO (or as 1 DO)
24 VDC, 20.4 ... 28.8 V
Yes (via optocoupler)
500 mA
2 mA
150 μs / 400 μs
75 μs / 100 μs
2 mA
Short circuit, ground fault and overload proof
Automatic restart after overload tripping
; low ("0") = 10% V
out
out
1
No
-12 ... +12 V
Equipment Manual, 07/2021, A5E33446720B
SIMOTION D410-2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotion d410-2Simotion d410-2 dpSimotion d410-2 dp/pn