Siemens SIMOTION Equipment Manual page 82

Hide thumbs Also See for SIMOTION:
Table of Contents

Advertisement

Technical data
5.2 Ambient conditions
• Humidity
• Strong magnetic fields
Use prohibition
Without additional measures, SIMOTION D410-2 must not be used in
• Locations with a high percentage of ionizing radiation
• Locations with extreme operating conditions, e.g.
– Dust accumulation
– Corrosive vapors or gases
• Installations requiring special monitoring such as:
– Elevator installations
– Electrical systems in particularly hazardous rooms
An additional measure for using SIMOTION D410-2 can, for example, be installation in cabinets.
Note
The components must be protected against conductive contamination, e.g. by installing them
in a control cabinet with degree of protection IP54 according to IEC 60529 or NEMA 12.
If conductive contamination can be excluded at the installation site, a lower degree of cabinet
protection may be permitted.
See Industrial security.
Ambient operating conditions for the operation
SIMOTION D410-2 can be used under the following ambient conditions:
Table 5-2
Environmental requirements
Ambient conditions
Climatic ambient conditions
Climate class
Permissible ambient temperature
Maximum installation altitude
Relative humidity
Condensation, icing, drip, spray and
splash water
Atmospheric pressure
Mechanical ambient conditions
82
Fields of application
3K3
0 to +55° C, up to 2000 m above sea
level
2000 m to max. 4000 m above sea
level
5 to 95%
Not permissible
620 to 1060 hPa
Remarks
According to EN 60721‑3:1995
Ambient conditions better than 3K3
As of an altitude of 2000 m, the maximum ambi‐
ent temperature decreases by 7 °C every 1000 m
increase in altitude.
Corresponding height 4000 m ‑ 0 m above sea
level.
Equipment Manual, 07/2021, A5E33446720B