ABB REF 610 Technical Reference Manual page 90

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

REF 610
90
Feeder Protection Relay
Technical Reference Manual
Table 4.1.16.3-1 Binary data
Description
Shot 3
CB position
Definite trip alarm signal
AR lockout signal
Open CB command
Close CB command
CB reclosing failed signal
CB reclosing inhibited
AR cancelled
PO1
PO2
PO3
SO1
SO2
SO3
SO4
SO5
DI1
DI2
DI3
DI4
DI5
Disturbance recorder
HMI password
IRF
Warning
SPA event overflow
Table 4.1.16.3-2 Analogue data
Description
Phase current I
x I
L1
n
Phase current I
x I
L2
n
Phase current I
x I
L3
n
Earth-fault current x I
n
Phase discontinuity x I
n
Thermal level
One-minute demand value
Demand value during the
specified time range
Maximum one-minute
demand value during the
specified time range
DNP point
Event
address
class
enable
23
1
24
1
25
1
26
1
27
1
28
1
29
1
30
1
31
1
32
1
33
1
34
1
35
1
36
1
37
1
38
1
39
1
40
1
41
1
42
1
43
1
44
1
45
1
46
1
47
1
48
1
49
1
DNP
Event
UR
point
class
enable
address
0
2
1
1
2
1
2
2
1
3
2
1
4
2
1
5
2
1
6
2
1
7
2
1
8
2
1
1MRS 755310
UR
Value
Comment
range
1
0/1
1 = initiated
1
0/1
1 = closed
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = triggered
0 = cleared
1
0/1
1 = opened
0 = closed
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
Internal
Value
Deadband
scaling
range
factor (ix=0)
1
0...5000
100
1
0...5000
100
1
0...5000
100
1
0...800
10
1
0...100
10
1
0...106
1
1
0...5000
100
1
0...5000
100
1
0...5000
100