The default class settings of the DNP points within the different event object groups
are:
• binary inputs change events: class 1
• analogue inputs change events: class 2
• counter change events: class 3
All static data points belong to class 0.
Unsolicited reporting is enabled for all event objects as default. However, the
point-specific enable/disable parameters are meaningless unless unsolicited
reporting has been enabled with SPA parameter 503V24.
The pointers to the scaling factors for analogue objects are all 0 as default.
Consequently, the DNP and Modbus analogue values of REF 610 are identical as
default.
All DNP process points can be edited using the Relay Setting Tool. Editing features
include:
• re-organizing, adding and removing DNP points
• assigning event classes to specific DNP points
• DNP point-specific enabling/disabling of unsolicited reporting
• defining deadbands for event reporting
• defining scaling factors for analogue values
Table 4.1.16.3-1 Binary data
Description
Start signal from stage I>
Trip signal from stage I>
Start signal from stage I>>
Trip signal from stage I>>
Start signal from stage I>>>
Trip signal from stage I>>>
Start signal from stage I
>
0
Trip signal from stage I
>
0
Start signal from stage I
>>
0
Trip signal from stage I
>>
0
Start signal from stage ∆I>
Trip signal from stage ∆I>
Start signal from stage θ>
Alarm signal from stage θ>
Trip signal from stage θ>
Trip signal from stage ARC
(light and current)
Trip signal from stage ARC
(DI and current)
Light signal output
Trip lockout signal
External trip signal
CBFP
Shot 1
Shot 2
DNP point
Event
address
class
enable
0
1
1
1
2
1
3
1
4
1
5
1
6
1
7
1
8
1
9
1
10
1
11
1
12
1
13
1
14
1
15
1
16
1
17
1
18
1
19
1
20
1
21
1
22
1
REF 610
UR
Value
Comment
range
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = detected
1
0/1
1 = activated
1
0/1
1 = activated
1
0/1
1 = failure
1
0/1
1 = initiated
1
0/1
1 = initiated