1MRS 755310
Feeder Protection Relay
Technical Reference Manual
100 ms
CB position closed
t
Shot Due
I>> Trip
Ext AR Initiation
I> Trip
I> start delay
t
I> Start *)
Io>> Trip
Io> Trip
Io> start delay
Io> Start *)
t
*) Shot initiation by a start signal applies only to shot 1 and definite tripping.
Fig. 4.1.4.8.-2 Simplified shot initiation logic diagram
Blocking of shot initiation
The initiation of one or several auto-reclose shots can be set to be blocked by any of
the following signals:
• external AR initiation signal
• trip signal from overcurrent stages I> and I>>
• trip signal from earth-fault stages I
The selection is made in SG1 (see table 4.1.4.10-10).
Blocking of shot initiation can also be used to skip the entire shot sequence (by
blocking the initiation of all three shots), and go directly to definite tripping. Further,
it can be used, for instance, to allow shot initiation by the trip signal from stage I>,
but to go directly to definite tripping in case of shot initiation by the trip signal from
stage I>>.
Note!
Activation of any above-mentioned signal will always cause the AR function to
issue an opening command to the circuit breaker. If the signal used for blocking is
not simultaneously used for initiation of the next shot, the AR function will generate
a definite trip alarm and be locked out.
Note!
Shot initiation is blocked only for as long as the blocking signal is active.
Note!
In case of shot initiation while a blocking is active, the next shot (if such has been
selected and not blocked) will be initiated. This can be used to skip Shot 1, for
instance.
OR
OR
OR
Blocking of shot
SG1/
1...8
> and I
>>
0
0
REF 610
AND
Shot Initiation
AND
Open CB Command
31