ABB REF 610 Technical Reference Manual page 55

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

1MRS 755310
Feeder Protection Relay
Technical Reference Manual
Table 4.1.4.10-9 SGL1...SGL8
Switch
Function
SGL1...8/9
Trip lockout signal
SGL1...8/10
Definite trip alarm signal from AR
SGL1...8/11
Shot due signal from AR
SGL1...8/12
Lockout signal from AR
SGL1...8/13
CB position open
SGL1...8/14
CB position closed
SGL1...8/15
DI1 signal
SGL1...8/16
DI2 signal
SGL1...8/17
DI3 signal
SGL1...8/18
DI4 signal
SGL1...8/19
DI5 signal
SGL1...8/20
Trip signal from stage ARC
SGL1...8/21
Light signal output
ΣSGL1...SGL8
Auto-reclose SG1...SG3
Switchgroup SG1 is used for blocking the initiation of one or several auto-reclose
shots, SG2 for blocking of protection stages at one or several auto-reclose shots, and
SG3 for inhibiting the AR function as follows:
Table 4.1.4.10-10SG1
Switch
Function
SG1/1
Blocking of initiation of shot 1 by the trip signal from stage
I>>
SG1/2
Blocking of initiation of shot 1 by the external AR initiation
signal
SG1/3
Blocking of initiation of shot 1 by the trip or delayed start
signal from stage I>
SG1/4
Blocking of initiation of shot 1 by the trip or delayed start
signal from stage I
SG1/5
Blocking of initiation of shot 2 and 3 by the trip signal from
stage I>>
SG1/6
Blocking of initiation of shot 2 and 3 by the external AR
initiation signal
SG1/7
Blocking of initiation of shot 2 and 3 by the trip or delayed
start signal from stage I>
SG1/8
Blocking of initiation of shot 2 and 3 by the trip or delayed
start signal from stage I
I
>>
0
• When the switch is in position 1, shot initiation is blocked.
ΣSG1
> or the trip signal from stage I
0
> or the trip signal from stage
0
REF 610
Default setting
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Default setting
0
0
0
0
>>
0
0
0
0
0
0
55