ABB REF 610 Technical Reference Manual page 105

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

1MRS 755310
Feeder Protection Relay
Technical Reference Manual
Recorded data
Parameter V1 shows the stage which has caused the trip, parameter V2 the trip
indication code, parameters V3...V8 show the number of starts of the protection
stages, parameters V9...V12 the number of trips of the protection stages, and
parameters V13...V24 the number of initiated auto-reclose shots.
Table 4.1.17-3 Recorded data: Channel 0
Recorded data
Stage/phase which caused the
trip
Trip indication code
Number of starts of stage I>
Number of starts of stage I>>
Number of starts of stage I>>>
Number of starts of stage I
Number of starts of stage I
Number of starts of stage ∆I>
Parameter (R)
V1
V2
V3
V4
V5
>
V6
0
>>
V7
0
V8
REF 610
Value
1=I
>
L3
2=I
>
L2
4=I
>
L1
8=I
>
0
16=I
>>
L3
32=I
>>
L2
64=I
>>
L1
128=I
>>
0
256=I
>>>
L3
512=I
>>>
L2
1024=I
>>>
L1
2048=∆I>
4096=θ>
8192=external trip
16384=AR
32768=trip of stage ARC (local)
65536=trip of stage ARC (remote)
0 = ---
1=start of stage I>
2=trip of stage I>
3=start of stage I>>
4=trip of stage I>>
5=start of stage I>>>
6=trip of stage I>>>
7=start of stage I
>
0
8=trip of stage I
>
0
9=start of stage I
>>
0
10=trip of stage I
>>
0
11=start of stage ∆I>
12=trip of stage ∆I>
13=alarm of stage θ>
14=trip of stage θ>
15=external trip
16=definite trip alarm
17=CB reclosing failed
18=AR shot due
19=AR lockout
20=trip of stage ARC
21=CBFP
0...999
0...999
0...999
0...999
0...999
0...999
105