ABB REF 610 Technical Reference Manual page 115

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

1MRS 755310
Feeder Protection Relay
Technical Reference Manual
Table 4.1.17-14Settings
SPA
parameter
Description
(channel
503)
Primary data link
503V4
layer
retransmission
count
Application layer
503V6
confirmation
timeout
Application layer
503V7
retransmission
count
Confirmation on
503V9
application layer
Default variation
503V10
of binary input
objects
Default variation
503V11
of binary input
change event
objects
Default variation
503V15
of analogue input
objects
Default variation
503V16
of analogue input
change event
objects
Default variation
503V13
of counter objects
Default variation
503V14
of counter change
event objects
Default variation
503V30
of frozen counter
objects
Class 1 event
503V18
delay
Class 1 event
503V19
count
Class 2 event
503V20
delay
Class 2 event
503V21
count
Class 3 event
503V22
delay
R, W Value range
Default Explanation
R, W 0...255
R, W 0...65535 ms
5000 Used when REF 610
R, W 0...255
R, W 0 = enabled only
for event
messages
1 = enabled for
all messages
R, W 1...2
R, W 1...2
R, W 1...4
R, W 1...4
R, W 1...2
R, W 1, 2, 5, 6
R, W 1, 2, 5, 6
R, W 0...255 s
R, W 0...255
R, W 0...255 s
R, W 0...255
R, W 0...255 s
REF 610
0
Number of
retransmissions on data
link layer
sends messages with
confirmation request
0
Number of
retransmissions on the
application layer when
REF 610 sends messages
with confirmation request
0
Used to enforce inclusion
of confirmation request in
all application messages
(DNP 3.0 standard
requires inclusion of
confirmation request in
event messages only)
2
2
2
2
2
2
2
0
1
0
1
0
115

Advertisement

Table of Contents
loading