ABB REF 610 Technical Reference Manual page 137

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

1MRS 755310
Feeder Protection Relay
Technical Reference Manual
Table 4.2.4-13 Standard tests
Insulation resistance measurements
• Isolation resistance
Mechanical tests
Vibration tests (sinusoidal)
Shock and bump test
Table 4.2.4-14 Data communication
Rear interface, connector X5.3, X5.4, X5.5 or X5.8
• Fibre-optic or RS-485 connection
• SPA bus, IEC 60870-5-103, DNP 3.0 or Modbus protocol
• 9.6 or 4.8 kbps (additionally 2.4, 1.2 or 0.3 kbps for Modbus)
Front interface
• Optical connection (infrared): wirelessly or via the front communication cable
(1MRS050698)
• SPA bus protocol
• 9.6 or 4.8 kbps (9.6 kbps with front communication cable)
Auxiliary voltage
REF 610 requires a secured auxiliary voltage supply to operate. The internal power
supply of the relay forms the voltages required by the relay electronics. The power
supply is a galvanically isolated (flyback-type) DC/DC converter. When the
auxiliary voltage is connected, the green indicator LED (ready) on the front panel
will be on. For detailed information on power supply, refer to table 4.2.4-2.
The primary side of the power supply is protected with a fuse located on the PCB of
the relay.
REF 610
According to IEC 60255-5
>100 MΩ, 500 V dc
According to IEC 60255-21-1, class I
According to IEC 60255-21-2, class I
137