Table 4.1.4.10-1 Setting values
Setting
Description
θ
Alarm level of stage θ>
>
a
CBFP
Operate time of CBFP
0→1
Number of AR shots
ArcI>
Current limit ArcI> of stage ARC
ArcI
>
Current limit ArcI
0
Setting range
50...100% θ
0.10...60.0 s
0 = AR is not in use
1 = shot 1
2 = shot 1 and 2
3 = shot 1, 2 and 3
0.50...35.0 x I
> of stage ARC
5.0...400% I
0
REF 610
Default setting
95% θ
>
>
t
t
0.10 s
0
2.50 x I
n
n
20.0% I
n
n