ABB REF 610 Technical Reference Manual page 84

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

REF 610
84
Feeder Protection Relay
Technical Reference Manual
Table 4.1.15.2-5 Mapping of Modbus data
Description
HMI password
HMI password CD
IRF
IRF CD
Warning
Warning CD
SPA event overflow
SPA event overflow CD
Recorded data
Fault record
Event record
Relay identification
Type designation of the relay
Real-time clock
Time reading and setting
Additional analogue
data
Thermal level
One-minute demand value
Demand value during the
specified time range
Maximum one-minute
demand value during the
specified time range
Stage/phase which caused
the trip
Trip indication code
Number of starts of stage I>
Number of starts of stage I>>
Number of starts of stage
I>>>
Number of starts of stage I
>
0
Number of starts of stage
I
>>
0
Number of starts of stage ∆I>
Number of trips of stage I>
Number of trips of stage I>>
Number of trips of stage I>>>
Number of trips of other
stages
Number of AR shots (shot 1)
initiated by the trip signal
from stage I>>
HR/IR
DI/Coil bit
address (.bit)
address
414.12
93
414.13
94
414.14
95
414.15
96
415.00
97
415.01
98
415.02
99
415.03
100
601...628
671...679
701...708
721...727
801
802
803
804
805 HI word
806 LO word
807
808
809
810
811
812
813
814
815
816
817
818
1MRS 755310
Value
Writeable
Comment
range
0/1
1 = opened
0 = closed
0/1
1 = activated
0/1
1 = activated
Only the CD bit
will be activated
in case of
overflow.
See Structure 2
See Structure 3
ASCII chars,
2 chars/register
W
See Structure 4
0...106
%
0...5000
0...50 x I
0...5000
0...50 x I
0...5000
0...50 x I
0...131071 See table
4.1.17-3
0...21
See table
4.1.17-3
0...999
Counter
0...999
Counter
0...999
Counter
0...999
Counter
0...999
Counter
0...999
Counter
0...65535
Counter
0...65535
Counter
0...65535
Counter
0...65535
Counter
0...255
Counter
n
n
n