ABB REF 610 Technical Reference Manual page 131

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

1MRS 755310
Feeder Protection Relay
Technical Reference Manual
Table 4.2.3-4
Receiver selection
Transmitter
Position of jumper X2
Plastic
X5.3-RX
Glass
X5.4-RX
Fibre-optic Interface
X5.3
TX
X5.4
TX
X5.3
RX
X5.4
RX
Fig. 4.2.3.-2
Jumper location on the communication module for plastic and
glass fibre
Table 4.2.3-5
Fibre-optic rear connectors (plastic and glass)
Terminal
Function
X5.3-TX
Transmitter for plastic fibre
X5.3-RX
Receiver for plastic fibre
X5.4-TX
Transmitter for glass fibre
X5.4-RX
Receiver for plastic fibre
RS-485 connection for the DNP 3.0 communication module
If REF 610 is provided with the optional DNP 3.0 communication module, the cable
is connected to terminals X5.8/1-2 and X5.8/4-8. The connection socket is a 8-pin
header-type socket and the terminals are of screw compression type.
The DNP communication module follows the DNP standard and is intended to be
used in a Daisy-chain bus wiring scheme with 2- or 4-wire, half-duplex, multi-point
communication. The maximum number of devices (nodes) connected to the bus
where REF 610 is being used is 32, and the maximum length of the bus is 1200
meters in optimum conditions and with slow communication speed.
X5.3-TX(plastic)
X5.3-RX(plastic)
X6
X2
X6
X2
X5.4-TX(glass)
X5.4-RX(glass)
REF 610