ABB REF 610 Technical Reference Manual page 153

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

1MRS 755310
Feeder Protection Relay
Technical Reference Manual
Table 9.-4 Parameters for the disturbance recorder
Description
External trigger signal's
checksum
External trigger signal's
edge
Checksum of external
signal storing mask
Table 9.-5 Auto-reclose parameters
Description
CB Closing time
Start delay of stage I>
Start delay of stage I
>
0
Reclaim time
Cutout time
Dead time of shot 1
Dead time of shot 2
Dead time of shot 3
SG1
SG2
SG3
Parameter
Setting range
(channel 0)
V241
0...31
V242
0...31
V243
0...31
Parameter
Value
(channel 0)
V121
0.1...10 s
V122
0...300 s
V123
0...300 s
V124
3...300 s
V125
0.1...300 s
V126
0.1...300 s
V127
0.1...300 s
V128
0.1...300 s
V129
0...255
V130
0...1023
V131
0...31
REF 610
Default
Customer's
setting
setting
0
0
0
Default
Customer's
setting
setting
0.2 s
300 s
300 s
10 s
0.1 s
0.3 s
30 s
30 s
0
0
15
153

Advertisement

Table of Contents
loading

Table of Contents