Feeder Protection Relay
Technical Reference Manual
Table 4.1.4.10-7 SGB1...SGB5
Switch
Function
SGB1...5/4
Switching between setting groups 1 and 2 using the digital input
• 0 = the setting group cannot be changed using the digital input
• 1 = the setting group is changed by using the digital input.
When the digital input is energized, setting group 2 will be
activated, if not, setting group 1 will be activated.
Note!
When SGB1...5/4 is set to 1, it is important that the switch has
the same setting in both setting groups.
SGB1...5/5
Time synchronization by the digital input signal
SGB1...5/6
External tripping by the digital input signal
SGB1...5/7
External triggering of the CBFP by the digital input signal
SGB1...5/8
External triggering of the trip lockout by the digital input signal
SGB1...5/9
External arc signalling by the digital input signal
SGB1...5/10
Resetting of the trip lockout by the digital input signal
SGB1...5/11
Blocking of tripping of stage I> by the digital input signal
SGB1...5/12
Blocking of tripping of stage I>> by the digital input signal
SGB1...5/13
Blocking of tripping of stage I
SGB1...5/14
Blocking of tripping of stage I
Blocking of tripping of stage ∆I> by the digital input signal
SGB1...5/15
SGB1...5/16
External AR inhibition by the digital input signal
SGB1...5/17
External inhibition of CB reclosing by the digital input signal
SGB1...5/18
CB position open
SGB1...5/19
CB position closed
SGB1...5/20
External AR initiation by the digital input signal
ΣSGB1...5
SGR1...SGR8
The start, trip and alarm signals from the protection stages, the signals from the
auto-reclose function, and the external trip signal are routed to the output contacts
with the switches of switchgroups SGR1...SGR8. The signals are routed to
PO1...PO3 with the switches of switchgroup SGR1...SGR3 and to SO1...SO5 with
those of SGR4...SGR8.
The matrix below can be of help when making the desired selections. The start, trip
and alarm signals from the protection stages, the signals from the auto-reclose
function and the external trip signal are combined with the output contacts by
encircling the desired intersection point. Each intersection point is marked with a
switch number, and the corresponding weighting factor of the switch is shown to the
right in the matrix. The switchgroup checksum is obtained by vertically adding the
weighting factors of all the selected switches of the switchgroup.
Note!
The trip lockout signal is always routed to PO3.
Note!
The trip signal from CBFP is always routed to PO2.
> by the digital input signal
0
>> by the digital input signal
0
1MRS 755310
Default
setting
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0