YASKAWA FP65U T Series Installation & Primary Operation page 91

Table of Contents

Advertisement

Code
Name
OD
Output Disconnect
oFA00
Option Not Compatible with Port
oFA01
Option Fault/Connection Error
oFA02
Duplicate Options
oFA03 to
Option Card Error Occurred at
oFA06
Option Port CN5-A
Option Card Error Occurred at
oFA10, oFA11
Option Port CN5-A
oFA12 to
Option Card Connection Error (CN5-
oFA17
A)
oFA30 to
Communication Option Card
oFA43
Connection Error (CN5-A)
oFb00
Option Not Compatible with Port
oFb01
Option Fault/Connection Error
oFb02
Duplicate Options
oFb03 to oFb11 Option Card Error Occurred at
Option Port CN5-B
oFb12 to oFb17 Option Card Error Occurred at
Option Port CN5-B
oH
Heatsink Overheat
oH1
Heatsink Overheat
oH3
Motor Overheat (PTC Input)
YASKAWA TOEPC7106171GA FP605 Drive Installation & Primary Operation
Causes
Speed search does not complete at start when A1-02
= 8 [EZ Vector Control] and you use an induction
motor.
The relay or contactor on the soft-charge bypass relay
is damaged.
An overcurrent condition occurred during
overexcitation deceleration.
The output circuit between the drive and the motor is
open, and the drive output current is less than 5% of
E2-01 [Motor Rated Current (FLA)].
The option connected to connector CN5-A is not
compatible.
The option card connected to connector CN5-A is not
compatible.
The same option cards or the same type of option
cards are connected to connectors CN5-A and B.
A fault occurred in the option card.
A fault occurred in the option card.
A fault occurred in the option card.
A fault occurred in the option card.
The option connected to connector CN5-B is not
compatible.
The option card connected to connector CN5-B was
changed during operation.
The same option cards or the same type of option
cards are connected to connectors CN5-A and B.
A fault occurred in the option card.
A fault occurred in the option card.
The ambient temperature is high and the heatsink
temperature of the drive is more than the value set in
L8-02 [Overheat Alarm Level].
The ambient temperature is high and the heatsink
temperature of the drive is more than the oH1
detection level.
The thermistor wiring that detects motor temperature
is defective.
20 Troubleshooting
Possible Solutions
When E9-01 = 0 [Motor Type Selection = Induction (IM)], set b3-
24 = 2 [Speed Search Method Selection = Current Detection Speed
Search].
• Re-energize the drive.
• If the fault stays, replace the control board or the drive.
• Decrease the value set in n3-13 [OverexcitationBraking (OEB)
Gain].
• Decrease the value set in n3-21 [HSB Current Suppression
Level].
Close the disconnected output circuit between the drive and the
motor.
Connect the option to the correct connector.
1.
De-energize the drive.
2.
Refer to the option card manual and correctly connect the
option card to the connector on the drive.
Connect the option card to the correct connector.
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
Connect the option to the correct connector.
Note:
The communication options cannot connect to connector CN5-
B.
1.
De-energize the drive.
2.
Refer to the option card manual and correctly connect the
option card to the connector on the drive.
Connect the option card to the correct connector.
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
• Measure the ambient temperature.
• Increase the airflow in the control panel.
• Install a cooling device (cooling fan or air conditioner) to lower
the ambient temperature.
• Remove objects near the drive that are producing too much heat.
• Measure the ambient temperature.
• Increase the airflow in the control panel.
• Install a cooling device (cooling fan or air conditioner) to lower
the ambient temperature.
• Remove objects near the drive that are producing too much heat.
Correct wiring errors.
91