12 Drive Control and Programming
No.
(Hex.)
H3-14
Analog Input Terminal Enable Sel
(041C)
H4-01
Terminal FM Analog Output Select
(041D)
H4-02
Terminal FM Analog Output Gain
(041E)
RUN
H4-03
Terminal FM Analog Output Bias
(041F)
RUN
H4-04
Terminal AM Analog Output
Select
(0420)
H4-05
Terminal AM Analog Output Gain
(0421)
RUN
H4-06
Terminal AM Analog Output Bias
(0422)
RUN
H4-07
Terminal FM Signal Level Select
(0423)
H4-08
Terminal AM Signal Level Select
(0424)
L1-01
Motor Overload (oL1) Protection
(0480)
L1-02
Motor Overload Protection Time
(0481)
L3-04
Stall Prevention during Decel
(0492)
o1-58
Motor Power Unit Selection
(3125)
60
Name
V/f
OLV/PM EZOLV
OLV/PM
Sets the enabled terminal or terminals when H1-xx = C [MFDI Function Select = Analog Terminal Enable Selection] is
ON.
1 : Terminal A1 only
2 : Terminal A2 only
3 : Terminals A1 and A2
4 : Terminal A3 only
5 : Terminals A1 and A3
6 : Terminals A2 and A3
7 : Terminals A1, A2, and A3
V/f
OLV/PM
OLV/PM EZOLV
Sets the monitor number to send from MFAO terminal FM.
V/f
OLV/PM
OLV/PM EZOLV
Sets the gain of the monitor signal that is sent from MFAO terminal FM.
V/f
OLV/PM EZOLV
OLV/PM
Sets the bias of the monitor signal that is sent from MFAO terminal FM.
V/f
OLV/PM EZOLV
OLV/PM
Sets the monitoring number to be output from the MFAO terminal AM.
V/f
OLV/PM
OLV/PM EZOLV
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
V/f
OLV/PM
OLV/PM EZOLV
Sets the bias of the monitor signal that is sent from MFAO terminal AM.
V/f
OLV/PM EZOLV
OLV/PM
Sets the MFAO terminal FM output signal level.
0 : 0 to 10 Vdc
2 : 4 to 20 mA
V/f
OLV/PM EZOLV
OLV/PM
Sets the MFAO terminal AM output signal level.
0 : 0 to 10 Vdc
2 : 4 to 20 mA
V/f
OLV/PM EZOLV
OLV/PM
Sets the motor overload protection with electronic thermal protectors.
0 : Disable
1 : Variable Torque
2 : Constant Torque 10:1 Speed Range
3 : Constant Torque 100:1 SpeedRange
4 : PM Variable Torque
5 : PM Constant Torque
6 : Variable Torque (50Hz)
V/f
OLV/PM EZOLV
OLV/PM
Sets the operation time for the electronic thermal protector of the drive to prevent damage to the motor. Usually it is not
necessary to change this setting.
V/f
OLV/PM EZOLV
OLV/PM
Sets the method that the drive will use to prevent overvoltage faults when decelerating.
0 : Disabled
1 : General Purpose
2 : Intelligent (Ignore Decel Ramp)
4 : Overexcitation/High Flux
5 : Overexcitation/High Flux 2
V/f
OLV/PM EZOLV
OLV/PM
Sets the setting unit for parameters that set the motor rated power.
0 : kW
1 : HP
Description
YASKAWA TOEPC7106171GA FP605 Drive Installation & Primary Operation