No.
(Hex.)
E2-01
Motor Rated Current (FLA)
(030E)
E2-11
Motor Rated Power
(0318)
H1-01 - H1-08
Term S1 to S8 Function Selection
(0438, 0439, 0400 -
0405)
H2-01
Term M1-M2 Function Selection
(040B)
H2-02
Term M3-M4 Function Selection
(040C)
H2-03
Term MD-ME-MF Function
Selection
(040D)
H3-01
Terminal A1 Signal Level Select
(0410)
H3-02
Terminal A1 Function Selection
(0434)
H3-03
Terminal A1 Gain Setting
(0411)
RUN
H3-04
Terminal A1 Bias Setting
(0412)
RUN
H3-05
Terminal A3 Signal Level Select
(0413)
H3-06
Terminal A3 Function Selection
(0414)
H3-07
Terminal A3 Gain Setting
(0415)
RUN
H3-08
Terminal A3 Bias Setting
(0416)
RUN
H3-09
Terminal A2 Signal Level Select
(0417)
H3-10
Terminal A2 Function Selection
(0418)
H3-11
Terminal A2 Gain Setting
(0419)
RUN
H3-12
Terminal A2 Bias Setting
(041A)
RUN
H3-13
Analog Input FilterTime Constant
(041B)
YASKAWA TOEPC7106171GA FP605 Drive Installation & Primary Operation
Name
V/f
OLV/PM
OLV/PM EZOLV
Sets the motor rated current in amps.
V/f
OLV/PM
OLV/PM EZOLV
Sets the motor rated output in the units from o1-58 [Motor Power Unit Selection].
V/f
OLV/PM EZOLV
OLV/PM
Sets the functions for MFDI terminals S1 to S8.
V/f
OLV/PM
OLV/PM EZOLV
Sets the function for MFDO terminal M1-M2.
V/f
OLV/PM EZOLV
OLV/PM
Sets the function for MFDO terminal M3-M4.
V/f
OLV/PM EZOLV
OLV/PM
Sets the function for MFDO terminal MD-ME-MF.
V/f
OLV/PM EZOLV
OLV/PM
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
2 : 4 to 20 mA
3 : 0 to 20 mA
V/f
OLV/PM
OLV/PM EZOLV
Sets a function for MFAI terminal A1.
V/f
OLV/PM EZOLV
OLV/PM
Sets the gain of the analog signal input to MFAI terminal A1.
V/f
OLV/PM
OLV/PM EZOLV
Sets the bias of the analog signal input to MFAI terminal A1.
V/f
OLV/PM EZOLV
OLV/PM
Sets the input signal level for MFAI terminal A3.
0 : 0-10V (Lower Limit at 0)
2 : 4 to 20 mA
3 : 0 to 20 mA
V/f
OLV/PM
OLV/PM EZOLV
Sets the function for MFAI terminal A3.
V/f
OLV/PM
OLV/PM EZOLV
Sets the gain of the analog signal input to MFAI terminal A3.
V/f
OLV/PM
OLV/PM EZOLV
Sets the bias of the analog signal input to MFAI terminal A3.
V/f
OLV/PM
OLV/PM EZOLV
Sets the input signal level for MFAI terminal A2.
0 : 0-10V (LowLim=0)
2 : 4 to 20 mA
3 : 0 to 20 mA
V/f
OLV/PM EZOLV
OLV/PM
Sets the function for MFAI terminal A2.
V/f
OLV/PM EZOLV
OLV/PM
Sets the gain of the analog signal input to MFAI terminal A2.
V/f
OLV/PM EZOLV
OLV/PM
Sets the bias of the analog signal input to MFAI terminal A2.
V/f
OLV/PM
OLV/PM EZOLV
Sets the time constant for primary delay filters on MFAI terminals.
12 Drive Control and Programming
Description
59

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fp605

Table of Contents