Troubleshooting - Danfoss R06 User Manual

Table of Contents

Advertisement

User Manual
R06 Receiver

Troubleshooting

400-900MHz Receiver LED troubleshooting
LED
Characteristic
POWER
Green; pulsing
HARDOK
Green; continuous
Red; pulsing
Red; other
SIGNAL
LED off
LED on + transmitter switched
off
LED on + DATA switched off
DATA
LED off + SINGAL LED on
Green; pulse
ID
LED off + DATA LED on
LED on + SIGNAL LED on +
DATA LED on
RELAY
Green
ORDER
Green
CANERR
Red | slow pulses
Red | double pulses
Red | 4 pulses
Red | 5 pulses
Red | continuous
CANRUN
Blinking Green
Solid Green
10 |
©
Danfoss | March 2019
The troubleshooting LEDs are located on the receiver board. Use the following table to identify faults and
corrective action.
In order to reach the signaling, the receiver must be accessible, connected, and the screws located on the
receiver lid must be unscrewed using the proper screw driver whenever the LEDs are not externally
visible.
The LEDs on the receiver board are POWER, HARDOK, SIGNAL, DATA, ID, ORDER and RELAY.
Please do check the following website for further information:
https://troubleshooting.dps-rct.com/en/customer-service-center
Description
Receiver is starting up
Receiver hardware OK
EEPROM error; data corruption; CAN bus error (if CANERR
activates)
Electronic board hardware breakdown
No radio signal detected
Radio channel occupied
Radio channel occupied by non Danfoss system
Radio error
Receiving good frames
No valid ID; Danfoss system nearby
Valid frames received from the transmitter; correct link
STOP relay activated
LED ON Whenever any output is ON
CAN Error, physical Layer
One expansion has Stopped working
A Transmitted CAN frame has been lost
A Received CAN Frame has been lost
CAN Bus OFF
Pre operational Status
Operational Status
Action
Wait until start-up process is
finished
Operate
Reprogram EEPROM
Replace device
-
Change transmitter's frequency
channel
Change transmitter's frequency
channel
Replace radio
OK
If channel not occupied, check
chosen ID in the transmitter or
reset the receiver
OK
-
-
Verify Connections
Verify Expansion boards
N/A
N/A
Verify CAN connections and
Status.
The Controller must set the CAN
Receiver to operational Status
OK
BC292460489593en-000201