Veeder-Root TLS2P Setup And Operation Manual page 76

Hide thumbs Also See for TLS2P:
Table of Contents

Advertisement

Reports
Alarm Reports
10 gallons [37.8 L] (whichever is greater), the alarm will deactivate. The Max Product value is entered as a volume with
the default value equal to 0. If the Max Product value is equal to 0 or the full tank volume capacity, the alarm is
disabled. An active Probe Low Temperature Warning will disable the alarm.
OVERFILL ALARM
If the product level volume exceeds the Overfill Alarm threshold and there is a delivery in progress, the Overfill Alarm
will activate. When the delivery stops, the alarm will deactivate. The Overfill alarm value is entered as a percentage
with the default value equal to 0%. An overfill threshold value of 0% disables the alarm. The overfill alarm threshold is
referenced to the Max Product value. If the Max Product value is 0, the overfill value is referenced to the Full volume
capacity. An active Probe Low Temperature Warning will disable the alarm.
LOW PRODUCT ALARM
If the product level volume is less than the Low Product threshold, the Low Product Alarm will activate. If the alarm is
active and the product level volume is higher than the threshold by at least 0.005 times the full volume capacity or 10
gallons [37.8 L] (whichever is greater), the alarm will deactivate. The Low Product value is entered as a volume with
the default value equal to 0. If the value is equal to 0, the alarm is disabled. An active Probe Low Temperature Warning
will disable the alarm.
HIGH WATER ALARM
If the water level height continuously exceeds the High Water threshold for a period exceeding 3 minutes, the High
Water Warning will activate. The high water alarm will not activate if there is a delivery in progress. If the alarm is active
and the water level height is lower than the threshold by at least 0.2 inches (5 mm), the alarm will deactivate. The High
Water value is entered as a height with the default value equal to 0. If the value is equal to 0, the alarm is disabled. An
active Probe Low Temperature Warning will disable the alarm.
PROBE OUT ALARM
If the console is not reliably communicating with the probe, the Probe Out alarm will activate.
INVALID FUEL HEIGHT
If the water float and the product float are too close together to provide reliable height data, the Invalid Fuel Height
alarm will activate.
PROBE LOW TEMPERATURE WARNING
Standard Probe: If the Probe is reporting a temperature lower than -4°F (-20°C), the Low Temperature warning will
activate. If the alarm is active and the temperature rises above 0°F (-17.7°C) the alarm will deactivate.
Low Temperature Probe: Alarm -40°F (-40°C), Clear -36°F (-37.7°). When the low temperature warning is active the
High Water, Low Product, Max Product, Delivery Needed, and Overfill alarms are disabled.
DELIVERY NEEDED ALARM
When the tank's product level drops below the preset limit, the Delivery Needed alarm will activate.
LEAK TEST ALARM
When a Gross, Periodic, or Annual leak test fails a Gross, Periodic, or Annual Leak Test Alarm will activate. To clear a
failed leak test alarm, a passing leak test must be run.