Page 1
Manual No: 577013-719 ● Revision: K TLS-IB Site Prep Manual Form Number 8466X0-180 Series (RS-232 w/IFSF) Form Number 8466X0-380 Series (RS-232 w/o IFSF) Form Number 8466X0-580 Series (RS-232/RS-485)
Page 2
Customer Service will work with production facility to have the replacement product shipped as soon as possible. If “lost” equipment is delivered at a later date and is not needed, Veeder-Root will allow a Return to Stock without a restocking fee.
Table of Contents 1 Introduction Related Manuals ......................1-1 Contractor Certification Requirements ................1-1 Safety Symbols ......................1-2 Control Drawing ......................1-3 2 Site Prep - International Installations General ..........................2-1 Installation Levels ....................2-1 In–Tank Probes .....................2-2 Health and Safety ......................2-3 General........................2-3 Danger Areas ......................2-3 Intrinsic Safety .......................2-3 TLS-IB Location ......................2-4 Mounting the TLS-IB ......................2-6...
Page 4
Table of Contents Optional RS-232 Serial Interface.................4-14 Signal Input Specifications ..................4-15 TLS-IB IFSF Commands ..................4-16 5 Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & RS-485 Probe Wiring Precautions ....................5-1 Probe Wiring Positions and Labeling..............5-1 Connecting Probes to the TLS-IB ..................5-1 Auto Probe Configuration ..................5-2 Manual Probe Configuration..................5-2 Connecting Serial Communication Wiring to the TLS-IB ..........5-3 J11/J12 Jumper Positions (Table 5-1)..............5-3...
Page 5
Table of Contents Table 4-1. TLS-IB IFSF Node Address Selections ..........4-4 Table 4-2. TLS-IB Serial Interface Connections ............4-15 Table 4-3. TLS-IB Serial Commands ..............4-15 Table 4-4. Tank Level Gauge Database ..............4-16 Table 4-5. Tank Level Gauge Error Code Database ..........4-16 Table 4-6.
576013-635 Veeder-Root RS-232 Serial Interface Manual Contractor Certification Requirements Veeder-Root requires the following minimum training certifications for contractors who will install and setup the equipment discussed in this manual: Installer Certification (Level 1): Contractors holding valid Installer Certification are approved to perform wiring and conduit routing;...
Introduction Safety Symbols Safety Symbols The following safety symbols may be used throughout this manual to alert you to important safety hazards and precautions. EXPLOSIVE FLAMMABLE Fuels and their vapors are extremely explosive if Fuels and their vapors are extremely flammable. ignited.
This system makes TLS-IB probes safe for use in a Class I, Group D hazardous location. TLS-IB probe wiring is intrinsically safe only when connected to Veeder-Root's TLS-IB Consoles. Reference Form Number 8466 TLS-IB Console and Form Numbers 8462, 8463, 8473, and 8493 (Probes).
Veeder–Root maintains a continuous process of product development and therefore product specifications may not be as described in this manual. Please contact the Veeder-Root office nearest you, or visit our website at www.veeder.com for information on new or updated products. Changes affecting products or procedures described in this manual will be reported in subsequent revisions.
24” (610mm) Minimum Probe length Install drop tube discharge oriented away from probe Figure 2-1. Determining The Minimum Mag Probe Length For further information on the performance, specification and selection of in-tank probes, please contact your local Veeder-Root representative.
INTRINSIC SAFETY The design of Veeder-Root products limits the power in the wiring to the in-tank probes and keeps this wiring physically separated from any other. It is the responsibility of the contractor to maintain the effectiveness of these safety features by preparing the installation site in accordance with the instructions and warnings which follow.
Site Prep - International Installations TLS-IB Location WARNING An explosion could occur if other wires share ducts with intrinsically safe probe wiring. Ducting from probes must not contain any other wiring circuits. FAILURE TO COMPLY WITH THIS WARNING COULD RESULT IN EXPLOSION, DEATH, SERIOUS PERSONAL INJURY, PROPERTY LOSS OR EQUIPMENT DAMAGE.
Site Prep - International Installations TLS-IB Location Alternative knockouts for cable entries IFSF cable (Optional) 1000 mm (Maximum) 1500 mm (Maximum) One 5 ampere fused, switched, neon indication spur (for 240 Vac), or a Conduit for probe dedicated circuit breaker field cables rated for 15 amperes, 120 Vac or 240 Vac.
Site Prep - International Installations Mounting the TLS-IB Mounting the TLS-IB Install the TLS-IB fastening devices to the mounting surface using the hole pattern 170 x 145mm (6.7 x 5.7 inches) shown in Figure 2-3. Mounting screws up to 4.7mm (3/16-inch) diameter may be used. Mount the TLS-IB to the mounting surface using the four mounting flanges on the back of the unit.
Site Prep - International Installations Cable Specifications Cable Specifications The cable type tables listed below form part of the individual system ATEX approval. WARNING Substitution of cable may impair intrinsic safety and may invalidate system approval. All specifications are in free air at +30°C: Table 2-1.
• The equipment must NOT be installed over or in a hazardous location. The RS-232 Interface can be used for direct local attachment of terminals if the cable run is no more than 15 metres. Veeder-Root do not guarantee proper equipment operation if RS-232 cable runs exceed 15 metres. NOTICE RS-232 cable runs longer than 15 metres could result in data errors.
1000 feet. Wire runs must be less than 1000 feet to meet intrinsic safety requirements. Splices Veeder-Root recommends that no splices be made in the wire run between a probe junction box and the console. Each splice degrades signal strength and could result in poor system performance.
The interior volume of each junction box must be a minimum of 16 cubic inches. Veeder-Root recommends the following junction boxes or equivalent: • Appleton Electric Co. - JBDX junction box, JBK-B cover, and JB-GK-V gasket.
Site Prep - U.S and Canadian Installations Mounting the TLS-IB If the intrinsically safe wires enter the building in a wiring trough, only intrinsically safe NOTICE wires (from TLS-IB probes) can be in the trough. Keep all low power (intrinsically safe) wiring physically isolated from high power wires in all wiring troughs per the NEC.
4 Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & With & W/O IFSF) This section applies only to TLS-IB consoles with the following Form Numbers: • 846620-180, 846660-180, 846690-180 (RS-232 with IFSF) • 846620-380, 846660-380, 846690-380 (RS-232 w/o IFSF) For Console Form Numbers 846620-580, 846660-580 and 846690-580 skip Section 4 and NOTICE proceed to Section 5.
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & With & W/O IFSF) Connecting Probes to the TLS-IB Connecting Probes to the TLS-IB Connect the two color-coded/marked wires from each probe to the appropriate connectors (e.g., Probe 1) of the Probe Terminal Block as shown in Figure 4-1. Observe polarity when connecting probe wires! NOTICE Connect probe cable shields and drain wires to ground in the TLS-IB only, not at the field junction boxes.
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & With & W/O IFSF) Connecting IFSF Wiring to TLS-IB Circuit directory label WARNING SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY. NO REPAIRS SHOULD BE ATTEMPTED. REFER SERVICING TO QUALIFIED PERSONNEL ONLY. PROBE 8 POWER Probe Wiring PROBE 7 Black wire from probe...
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & With & W/O IFSF) Connecting IFSF Wiring to TLS-IB 1. With AC power switched Off, connect the IFSF network wires to J8 in the TLS-IB as shown in Figure 4-2 below: PROBE 4 LON Bus Termination PROBE 3 LON bus cable termination PROBE 2...
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & With & W/O IFSF) Connecting Serial Communication Wiring to the TLS-IB Table 4-1. TLS-IB IFSF Node Address Selections Dip Switch Setting IFSF Address Connecting Serial Communication Wiring to the TLS-IB With AC power switched Off, connect the serial communication wiring to J7 in the TLS-IB as shown in Figure 4-3. REFER SERVICING TO QUALIFIED PERSONNEL ONLY.
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & With & W/O IFSF) Connecting Power Wiring to TLS-IB Connecting Power Wiring to TLS-IB WARNING The TLS-IB contains voltages which can be lethal. It is connected to devices that must be intrinsically safe. FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND SAFETY PRECAUTIONS COULD CAUSE DAMAGE TO PROPERTY, ENVIRONMENT, RESULTING IN SERIOUS INJURY OR DEATH.
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & With & W/O IFSF) Connecting Power Wiring to TLS-IB WARNING! Shock hazard. Do not touch metal ends of WARNING capacitors C26/C28 Power Wiring SUBSTITUTION OF COMPONENTS or the metal bands MAY IMPAIR INTRINSIC SAFETY. on chokes L2/L4.
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & With & W/O IFSF) Troubleshooting Troubleshooting This section contains information to help you diagnose system problems. Instructions are included for replacing CPU and Power Supply boards in the event of a hardware failure and for installing a software upgrade. Also, the location and use of the neuron service switch is discussed.
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & With & W/O IFSF) Troubleshooting PROM CHIP REPLACEMENT (SOFTWARE UPGRADE) The PROM chip (U29) is replaced when a software upgrade is installed. This procedure requires that you perform a RAM clear. 1. If possible, record the current setup information. Switch Off power to the system. 2.
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & With & W/O IFSF) Troubleshooting Probe Status POWER Indicator (LED1) Clear RAM RAM Clear Jumper (J4) shown in Normal position. You must move jumper to LED1 middle and right pins to clear RAM: SERVICE IFSF 331470 R12-001...
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & With & W/O IFSF) Troubleshooting STATIC SENSITIVE - WEAR GROUNDED ANTI-STATIC WRIST STRAP BEFORE HANDLING THIS BOARD! PROM chip (U29) NODE 1) Orient PROM so that the small indented dot on ADDRESS top of the chip is on the same side with the small TLS-IB CPU BOARD triangle embossed in the socket's base;...
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & With & W/O IFSF) TLS-IB Specifications 5. Replace the board by reversing the above steps. 6. Switch On power to the TLS-IB and check your system configuration for proper setup. NEURON SERVICE SWITCH To manually transmit the TLS-IB neuron ID, press S1 (service switch) shown in Figure 4-9. The figure also locates the IFSF LED (D1) which indicates if the neuron application is, or is not, running.
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & With & W/O IFSF) TLS-IB Specifications ENVIRONMENTAL SPECIFICATIONS • TLS-IB storage and operation: indoor, climate controlled. • Operating temperature range: 0 to +40 °C. • Storage temperature range: -40 to +74 °C. • LVD and EMC compliant. •...
TXD (pin 2) B (transmit) RXD (pin 3) G (signal ground) GND (pin 7) • Veeder-Root RS-232 command protocol format applies. Table 4-3 lists serial commands recognized by the TLS- Table 4-3. TLS-IB Serial Commands Command Description System Reset Clear Power Reset Flag...
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & With & W/O IFSF) TLS-IB Specifications TLS-IB IFSF COMMANDS The IFSF commands recognized by the TLS-IB are divided into 5 databases; Tank Level Gauge Database (Table 4-4), Tank Level Gauge Error Code Database (Table 4-5), Tank Probe Database (Table 4-6), Tank Temperature Table Database (Table 4-7), and Tank Probe Error Code Database (Table 4-8).
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & With & W/O IFSF) TLS-IB Specifications Table 4-6. Tank Probe Database Data Identification Data Element Name TP_Serial_Nb TP_Model TP_Appl_Software_Ver TP_Status TP_Alarm Product_Level Water_Level TP_Status_Message Table 4-7. Tank Temperature Table Database Data Identification Data Element Name Temp_height Temp_value Table 4-8.
5 Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & RS-485 This section applies only to TLS-IB consoles with the following Form Numbers: 846620-580, 846660-580, 846690-580 (RS-232/RS-485) WARNING The equipment is used in location where lethal voltages and explosive vapors or flammable fuels may be present. FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND SAFETY PRECAUTIONS COULD CAUSE DAMAGE TO PROPERTY, ENVIRONMENT, RESULTING IN SERIOUS INJURY OR DEATH.
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & RS-485 Connecting Probes to the TLS-IB Observe polarity when connecting probe wires! NOTICE Connect probe cable shields and drain wires to ground in the TLS-IB only, not at the field junction boxes. Do not ground both ends of the shield.
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & RS-485 Connecting Serial Communication Wiring to the TLS-IB Connecting Serial Communication Wiring to the TLS-IB With AC power switched Off, connect the serial communication wiring to J3 in the TLS-IB as shown in Figure 5-2. Serial Comm Wiring For RS-232 Network: Connect TX to (B)
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & RS-485 Connecting Power Wiring to TLS-IB Table 5-1. J11/J12 Jumper Positions Jumper(s) Position Result Right -------- J12A ( Follow instructions provided by Clears RAM V-R Tech Support) Left Connecting Power Wiring to TLS-IB WARNING The TLS-IB contains voltages which can be lethal.
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & RS-485 Connecting Power Wiring to TLS-IB WARNING! Shock hazard. Do not touch metal ends of capacitors C53/C60 or the metal bands Power Wiring on chokes L4/L3. Connect neutral wire to upper terminal of J2 (N). Connect PROBE 8 hot wire to lower terminal (L).
3-wires stripped wires on the other end that will connect to the Serial Comm plug (J3) on the TLS-IB CPU/ Power Supply board (ref. Table 5-2 on page 5-9 for pin outs). • The TLS-IB.exe program and Firmware Upgrade file - available from Veeder-Root. • A laptop running Windows 7 or later software.
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & RS-485 Troubleshooting C:\Program Files (x86)\Veeder-Root\TLS-IB\349876-001A.txt Status Window Figure 5-4. TLS-IB Firmware Update Screen 8. Select the Comm Port of the connected laptop using the up/down arrows of the Comm Port selector. 9. Select the communication parameters, Baud Rate, Parity, Data and Stop Bit to connect to the TLS-IB using the up/down arrows for each selection.
GND (pin 5 DB9, pin 7 DB25) RS-485 Serial Interface A (receive) B (transmit) G (signal ground) SERIAL INTERFACE COMMANDS Veeder-Root RS-232 command protocol format applies. Table 5-3 lists the serial commands recognized by the TLS-IB: Table 5-3. TLS-IB Serial Commands Command Description System Reset...
Page 46
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & RS-485 TLS-IB Specifications Table 5-3. TLS-IB Serial Commands Command Description Set Euro-Protocol Prefix Set TC Density Enable Set Tank Configuration Set Tank 1 Point Full Height Volume Set Tank 4 point Full and 3/4, 1/2, 1/4 Volumes Set Tank 20 Point Full, 95%, 90%,.
Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & RS-485 TLS-IB Specifications RESPONSE MESSAGE FORMAT FOR FUNCTION CODE 64C The Set Field Density And Temperature (64C) Function Code is applicable to TLS-IB Form Numbers 846620- 580, 846660-580 and 846690-580 only. Function Code: Function Type: Set Field Density/Temperature Measurement Command Format: Display: <SOH>S64CTTDD.tttTTT.hh<SOH>I64CTT or: <SOH>S64CTTDD.t,TT.h...