Key
IDNet – allows you to select an IDNet or VESDA
point.
P / A / L – allows you to select a digital (P), analog
(A), or List (L) pseudo point.
NET - allows you to select a network point
ADDR - sw address of the point in the system
page 19
Table 2: Keypad Use
Data to Enter
C-D, followed by ENTER, where C represents the IDNet, or VESDA channel and D
represents the device number. You must insert the dash between channel and device.
Use the NET key to insert the dash.
Note:
• IDNet. Specify the channel with a number from 1 through 10. Use the number 0
to represent channel 10. Device numbers run from 1 to 250.
• VESDA. Specify the channel then the device. Device numbers on each VESDA
channel run from 1 to 127.
Enter the number corresponding to the digital pseudo, analog pseudo, or list point. For
example, pressing the P key and entering a 1 selects P1, the Alarm Silence Key pseudo
point.
Enter a network NODE number, followed by ENTER. The system then prompts for the
type of point you want to select. Press the keypad key corresponding to the type of
point (Zone, Signal, etc.) Use the descriptions above for information on selecting the
specific point.
Specify the address using the format C-P-S, where C is the card, P is the point, and S is
the subpoint. You must insert the dash between the components of the address. Use
the NET key to enter the dash.