Huawei SmartLi 2.0 User Manual page 104

Hide thumbs Also See for SmartLi 2.0:
Table of Contents

Advertisement

SmartLi 2.0
User Manual
Table 6-3 Running status
No.
Check
Item
1
Battery
running
status
2
Indicators
on the
panel of
the BCU
3
Battery
SOC
4
Shallow
discharge
test
(recomme
nded)
5
Capacity
test
(recomme
nded)
Issue 10 (2022-04-30)
Acceptance Criteria
The operating status displayed
on the LCD is charging or
discharging, and no fault or
alarm information is displayed.
The green indicator is on, and
the yellow (ALARM) and red
(FAULT) indicators are off.
Charge the battery
continuously for at least one
week and record the battery
SOC (normally the SOC is
100%).
During the shallow discharge
test, no fault or alarm is
displayed on the LCD.
During the capacity test, no
fault or alarm is displayed on
the LCD.
Copyright © Huawei Technologies Co., Ltd.
Check Method
● Check method: Visual
inspection. Check the status
displayed on the SmartLi
LCD.
● Troubleshooting: View the
alarm information on the
LCD and handle the alarm.
● Check method: visual
inspection
● Troubleshooting: View the
alarm information on the
LCD and handle the alarm.
● Check method: Visual
inspection. Check the SOC of
each module on the SmartLi
LCD.
● Troubleshooting: Charge the
battery until the SOC is
100%.
● Check method: Perform a
shallow discharge test by
referring to
6.2 Shallow
Discharge Test
and check
the alarm information on
the SmartLi LCD.
● Troubleshooting: View the
alarm information on the
LCD and handle the alarm.
● Check method: Perform a
capacity test by referring to
6.3 Capacity Test
the alarm information on
the SmartLi LCD.
● Troubleshooting: View the
alarm information on the
LCD and handle the alarm.
6 Maintenance
Recomm
ended
Check
Interval
Monthly
Monthly
Monthly
Quarterly
Annually
and check
97