Huawei SmartLi 2.0 User Manual page 102

Hide thumbs Also See for SmartLi 2.0:
Table of Contents

Advertisement

SmartLi 2.0
User Manual
No.
Check
Item
6
Ambient
humidity
Table 6-2 Product components
No.
Check
Item
1
Cabinet
appearanc
e
2
Battery
appearanc
e
3
Cabinet
cable hole
protection
4
Cabinet air
exhaust
vent
Issue 10 (2022-04-30)
Acceptance Criteria
Actual humidity: ______% (0–
95% RH, non-condensing)
Acceptance Criteria
The cabinet is free from dust
(on air filters and fans), rust,
and deformation.
● Batteries are free from
stains.
● Battery wiring terminals are
intact.
● Batteries are intact and free
of damage, deformation,
bulges, and cracks.
● Batteries have no electrolyte
leakage. (If electrolyte
leakage occurs, there will be
a pungent smell.)
The cable holes of the lithium
battery cabinet have been
sealed using the standard
sealing plates or glands, and
rodent-proof measures are
taken.
The upper air exhaust vent of
the lithium battery cabinet is
not blocked.
Copyright © Huawei Technologies Co., Ltd.
Check Method and
Troubleshooting
● Check method: Measure
using a hygrothermograph.
● Troubleshooting: Check that
the air conditioner runs
properly.
Check Method and
Troubleshooting
● Check method: visual
inspection
● Troubleshooting: Rectify the
fault based on the
acceptance criteria.
● Check method: visual
inspection
● Troubleshooting: Contact
technical support.
● Check method: visual
inspection
● Troubleshooting: Rectify the
fault based on the
acceptance criteria.
● Check method: visual
inspection
● Troubleshooting: Rectify the
fault based on the
acceptance criteria.
6 Maintenance
Recomm
ended
Check
Interval
Monthly
Recomm
ended
Check
Interval
Monthly
Monthly
Monthly
Monthly
95

Advertisement

Table of Contents
loading

Table of Contents