PROFINET IO
4.1 Parameters/address space
Input delay
This parameter can be used to suppress signal interference. Changes to the signal are only
detected if they are present consistently for longer than the set input delay time.
In isochronous mode, the terminal signal is read in at the time T
data). The read-in time T relates to the channel for which an input delay time of 0.05 ms was
configured.
For input channels with longer input delays, the read-in time is moved accordingly. This
means individual channels can be assigned input delays, if necessary, without having a
negative impact on the possible cycle time.
Isochronous configuration is only possible if there an input delay of 0.05 ms is configured for
at least one channel. Otherwise, the "Parameter assignment error" diagnostics alarm is
output.
Hardware interrupt on rising edge
Specifies whether a hardware interrupt is generated for a rising edge on the channel.
Hardware interrupt on falling edge
Specifies whether a hardware interrupt is generated for a falling edge on the channel.
4.1.3

Address space

The DI 8x24VDC M12-L 8xM12 I/O device can be configured differently; see following table.
Depending on the configuration, additional/different addresses are assigned in the process
image input.
Configuration options of the DI 8x24VDC M12-L 8xM12 I/O device
You can configure the I/O device with STEP 7 (TIA Portal) or with a GSD file.
When you configure the I/O device by means of the GSD file, the configurations are available
under different short designations/device names in the device view of your configuration
software.
22
I/O device digital inputs DI 8x24VDC M12-L 8xM12 (6ES7141-6BG00-0BB0)
Equipment Manual, 02/2022, A5E46570417-AC