4.2 Interrupts/diagnostics alarms
4.2.3

Alarms

4.2.3.1

Diagnostics alarms

A diagnostics alarm is output for each diagnostics event. On the I/O device
DI 8x24VDC M12-L 8xM12 the LED ER/MS flashes red. You can read out the diagnostics
alarms in the diagnostics buffer of the CPU, for example. You can evaluate the error codes
with the user program.
Table 4- 6
Diagnostics alarms, their meanings and corrective measures
Diagnostics alarm
Error code
Wire break
6
H
Parameter error
10
Hardware interrupt
16
lost
Short-circuit to
106
ground
30
Meaning
Fault in the external circuitry
Encoder faulty
Load resistance too high
Impedance of encoder circuitry is too high Use a different encoder type or modify
Interruption of cable between the I/O
device and sensor.
Channel not connected (open)
I/O device cannot evaluate parameters
H
for the channel
Incorrect parameter assignment
The I/O device cannot trigger an interrupt
H
because the previous interrupt was not
acknowledged; possible configuration
error
Short-circuit to ground
H
Corrective measures
Check the external circuitry and correct
the fault.
Replace the encoder.
Reduce the load resistance.
the wiring. For example, use cables with a
larger cross-section.
Establish the connection.
Correct the parameter assignment.
I/O device digital inputs DI 8x24VDC M12-L 8xM12 (6ES7141-6BG00-0BB0)
Equipment Manual, 02/2022, A5E46570417-AC
Disable diagnostics
Connect a resistor of 25 kΩ to 45 kΩ
to the encoder contacts.
Change the interrupt handling on the
CPU. Reassign the parameters to the
I/O device, if necessary.
The error persists until the I/O device is
assigned new parameters.
Correct the process wiring.
Replace the defective encoder.