2.2.2 DC Power Supply Wiring and Grounding

Figure 5 - DC Power supply wiring and grounding diagram

The RS940G low voltage DC power supply features reverse polarity protection and dual
independent inputs. The latter feature allows the connection of two DC sources with the same
nominal voltage to provide redundant power supply inputs.
The RS940G DC power supply inputs should be connected as follows:
1. Connect to the DC inputs according to the polarity markings on the unit.
2. Surge Ground should be connected to the Chassis Ground via a braided cable or other
appropriate grounding wire. Surge Ground is used as the ground conductor for all surge
and transient suppression circuitry internal to the unit.
3. Chassis Ground must be connected to the protective earth.
NOTES:
1. Equipment must be installed according to the applicable country wiring codes.
2. All line-to-ground transient energy is shunted to the Surge Ground terminal. In cases
where users require the inputs to be isolated from ground, remove the ground braid
between Surge and Chassis Ground. Note that all line-to-ground transient protection
circuitry will be disabled.