Gnd Terminals Connection; Line Termination Rt; Power Supply Connection; Start-Up - CEL-MAR ADA-4040PC8 User Manual

Table of Contents

Advertisement

ADA-4040PC8

3.3.3. GND TERMINALS CONNECTION

Connection of GND terminals of RS485/422 interfaces, devices connected to RS485/422 bus, should be done in the case of a
potential difference of the signals grounds on interfaces RS485 / RS422, which prevents proper data transmission.
Cannot connect to the GND terminal - cables screens, PE circuit of electrical installation, signals grounds of other devices.

3.3.4. LINE TERMINATION Rt

The application of Line Termination (terminator) Rt = 120 ohms will reduce electrical reflection in data line at high baud rate. It is not
needed below 9600Bd. Should be used the Line Termination resistor if the distance is over 1000m @ 9600Bd or 700m @ 19200Bd,
and if the disturbance in transmission will appear. Example connection of Rt are shown on the figures below. Four Rt=120 W , 0,25W
are delivered with the converters.

3.4. POWER SUPPLY CONNECTION

We recommend for powering of ADA-4040PC8 to use individual, stabilized power supply with output voltage from 10 V= to 30V=, min.
nominal power 2W, e.g. HDR-15-24. Power cable from DC power supplies to device can not be longer than 3m. Should connect
positive (+) end of DC power supplies to V+ device terminal and negative (-) end to V- on terminal block.
ADA-4040PC8 has protection against power supply reverse connection.

4. START-UP

The converter can be power on after properly connection according to section above.
If after connection power supply on front panel will not light green led PWR, check correctness of power supply connecting
(polarization). When data is present the LEDs Tx and Rx should blink
AT BAUD RATE ABOVE 38.4 KBPS OF THE TX DIODE, MORE POORLY WILL LIGHT RX DURING THE DATA TRANSFER

4.1. DESCRIPTION OF SIGNALLING LEDS

LED
PWR
RX
TX
Yellow LED by SW1

4.2. TROUBLESHOOTING

Problem
PWR LED is not lit
Rx LED lights
continuously
No transmission
Tx LED is blinking

5. CONFIGURATION

5.1. OPERATION MODE

ADA-4040PC8 converter can operates in and few modes:
● RUN,
● configuration,
● factory default,
● emergency firmware update mode,
Those modes can be set by use SW1 located by terminal block JCT port. To set the switch section, should remove terminal cover
marked as SW1 and make the appropriate settings by the use a small, flat screwdriver.
All available adjusting the SW1 switch are shown in table below.
Operation modes
SW1 - 1
SW1 - 2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Emergency firmware update
Signalling of Power Supply
Signalling of data receiving through ADA-4040PC8 from RTU RS485/RS422 port.
Signalling of data transmitting from ADA-4040PC8 through RTU RS485/RS422 port.
Not light – signalling of normal operating mode (RUN)
Blinking at frequency 1 Hz - signalling of configuration mode or data flow of software to the converter.
Blinking at frequency 2 Hz - signalling of factory default mode
Lit continuously – signalling of emergency firmware update
Check polarization and parameters of connected power supply.
RS485(4W) /422 network. Wrong polarization on terminals: Rx+, Rx- RTU port; change polarization.
RS485(4W) / RS422 network. Check correctness of connection to terminals Tx, Rx; according to
point 3 and the converter configuration.
Mode
Run
Configuration
Flashes every 1 sec.
Factory default
Flashes every 0,5 sec.
ATTENTION!
Description
Solutions
Yellow LED
Not lit
Continuous light
7