Troubleshooting
April 2022
Table 2-2: Troubleshooting
Error
Flow pressure is outside
the alarm limits
22
Maintenance and Troubleshooting Manual
(continued)
Recommended action(s)
Startup issues:
Verify that there is voltage to the pressure sensor from either
the meter's power supply board or from an external power
supply.
If using an analog pressure device, verify that the pressure
sensor is properly wired to the connector.
Verify the input is properly configured for your pressure input.
If using a flow computer to write pressure to the meter, verify
that it is properly writing to fixed flow pressure in the proper
units.
Run time issues:
Adjust pressure of process fluid to within alarm limits.
If using an analog pressure device and input reading is 0, check
if IsAI1Avail is equal to 1 in the Meter Information dialog in
MeterLink. If it is not 1, either the I/O Board has been removed
or is damaged. Reinstall or replace the board if this value is 0.
If using an analog pressure device, verify that the pressure
sensor is working properly.
If using an analog pressure device, recheck wiring and switch
settings.
If a flow computer is writing values to the fixed flow pressure,
verify that the flow computer is still writing valid values without
Modbus write errors.
Reverify the pressure input settings are correct.