Download Print this page

Simplex 4100-9401 Assembly/Installation Instructions page 6

Remote display
Hide thumbs Also See for 4100-9401:

Advertisement

Installing the Remote Display Assembly,
1.
Insert a mounting screw in both the top right and top left mounting holes in the back box.
Install the
Remote Box
2.
Tighten the two mounting screws, but leave a 1/8-inch (3-mm) gap from the seated position of each
screw.
3.
Insert the remaining mounting screws through the screw holes in the box
4.
Tighten all mounting screws securely.
1.
Re-attach the TIC module to the back box.
Re-attach
Assembly
2.
Attach the Flexible User Interface by slotting the bottom tabs through the swivel standoffs at the
bottom of the back box, and pressing the latch in to secure the panel assembly.
3.
Re-attach the grounding wires between the panel assembly and the back box
4.
Connect harness 734-008 from either P7 or P9 on the Flexible User Interface controller card to P2
on the TIC card.
5.
Replace the door on its hinge and reattach grounding strap.
Switches SW1 on the Flexible User Interface Controller Board and the TIC are each a bank of eight dip
Configure
Switch Address
switches. From left to right (see Figure 5 below) these switches are designated as SW1-1 through SW1-
8. The function of these switches is as follows:
SW1-1. This switch sets the baud rate for the internal FACP communications line running between
the card and the FACP CPU. Set this switch to ON.
SW1-2 through SW1-8. These switches set the card address for the FACP. Refer to Table 1 for a
complete list of the switch settings for all of the possible card addresses.
Note:
Each card must be set to the address assigned in the FACP programmer.
Figure 5. Internal Baud/Address DIP switch
firealarmresources.com
continued
6

Advertisement

loading

This manual is also suitable for: