8. If you removed any fabric modules before moving the chassis, replace each one in the chassis as
follows:
a) Holding the front of the fabric module (the side with the LEDs), turn the module so that the front
side is vertical.
Note : The top of the module has an alignment bracket running from the rear to the front. The
electrical connectors will be at the bottom.
b) Align the rear of the fabric module to an open fabric slot and insert the bracket on top of the
module into the track at the top of the slot.
Note : If there are only three fabric modules to install, install them in fabric slots 1, 3, and 5, and
be sure that there are blank filler plates installed in the open slots.
c) Slide the module part way into the slot.
d) Press the ejector button on the front of the module, to release the levers from the front of the
module.
e) Rotate the levers away from the front of the module and hold them while sliding the module all the
way into the slot.
f) Simultaneously rotate both levers to the front of the module. They click when locked to the front
of the module.
9. If you removed any fan modules before moving the chassis, reinstall each one in the chassis as
follows:
a) Holding each of the two handles on the fan module with your two hands, align the fan module to
an open fan module slot.
Note : The two alignment brackets on top of the fan module should align to two tracks at the top
of the slot.
b) Slide the fan module into the slot until the front of the fan module comes in contact with the rear
of the chassis.
Note : The two alignment pins on the fan module (on the top and one on the bottom) should go
into holes in the chassis and the four captive screws on the fan module should align to screw holes
in the chassis.
c) Screw in the four captive screws to the chassis and tighten each screw to 8 in-lb (0.9 N-m).
10. If you removed any power supplies before moving the chassis, reinstall each one as follows:
a) Determine which power supply slots to fill and ensure that each of those slots is open.
b) If you are using the combined or power supply redundancy mode, you can use any slot for the
power supply that you are installing.
If you are using input-source or full redundancy mode, you must group the power supplies that are
to be connected to the same grid on either the left or right power supply slots in the chassis (that
74  IBM Storage Networking SAN192C-6, SAN384C-6 and SAN768C-6: SAN192C-6, SAN384C-6 and
SAN768C-6 Installation, Service, and User Guide